Chapter 4 Parameter Index
http://www.acdrive-china.com
67
Function
code
Function
Name
LCD Display
Range of
settings
Default
Change
MODBUS
Address
P2.01
Acc time of
Jog
Acc time of
Jog
3132G/3160P
or below:
0.1
~
3600s
3160G/3185P
or above:
1.0
~
3600s
○
0301
P2.02
Dec time of
Jog
Dec time of
Jog
3132G/3160P
or below:
0.0
~
3600s
3160G/3185P
or above:
0, 1.0
~
3600s
3022G/
3030P
or
below:
6.0s
3030G/
3037P
or
above:
20.0s
○
0302
P2.03
Switching
time
between run
forward and
reverse
Switching
time
between run
forward and
reverse
0.0
~
3600s
0.0s
○
0303
P2.04
Frequency
lower limit
deal mode
Frequency
lower limit
deal mode
0: Running at
frequency
Lower limit
1: Zero-speed
running
0
× 0304
P2.05
Frequency
departure
setting
Frequency
departure
0.00-2.50Hz 0.00Hz
○
0305
P2.06
Carrier
frequency
Carrier
frequency
This value
depends on the
ac drive model
This
value
depend
s on the
ac
drive
model
× 0306
P2.07
Jump
frequency 1
Jump
frequency 1
0.00~Max
frequency
0.00Hz
× 0307