![Alpha ALPHA6000 Series Manual Download Page 64](http://html1.mh-extra.com/html/alpha/alpha6000-series/alpha6000-series_manual_2905270064.webp)
Chapter 4 Parameter Index
http://www.acdrive-china.com
64
P1: Start/Stop Control
Function
code
Function
Name
LCD
Display
Range of settings
Default
Change
MODBUS
Address
P1.00
Starting
mode
Starting
mode
0: Start directly
1: Brake first and
then start at start
frequency
2: Start after speed
tracking (the
mode is only valid
for the motor of
35R5GB/37R5PB
or above)
Note: the startup
includes power on,
power recovery after
an instantaneous off,
external fault reset,
and restart after
coast to stop.
0
○
0200
P1.01
Starting
frequenc
y
Starting
frequency
0.10
~
60.00Hz
0.50Hz
○
0201
P1.02
Starting
frequenc
y holding
time
Starting
holding
time
0.0
~
10.0s
0.0s
○
0202
P1.03
DC
injection
braking
current at
start
Brake
current at
start
Type G: 0.0
~
100.0% of ac drive
rated current
Type P: 0.0
~
80.0%
of ac drive rated
current
0.0%
○
0203
P1.04
DC
injection
braking
time at
start
Brake
time at
start
0.0
~
30.0s
0.0s
○
0204
P1.05
Acc/Dec
mode
Acc/Dec
mode
0: Linearity
1: S-curve
2: (Reserved)
3: (Reserved)
0
○
0205