Appendix 4 MODBUS Communication
http://www.acdrive-china.com
230
Example: 30.00 Hz frequency reference is saved in EEPROM.
Slave Address
01
Function Code
10
Starting
No.
Upper
01
Lower
00
Quantity
Upper
00
Lower
01
No. of Data
02
Data
Upper
0B
Lower
B8
CRC
Upper
B1
Lower
D2
Slave Address
01
Function Code
90
Error Code
23
CRC
Upper
0D
Lower
D9
Command Message
Normal Response Message AbnomalResponse Message
(ENTER)
(Frequency Reference Write)
Slave Address
01
Function Code
10
Starting
No.
Upper
00
Lower
FF
Quantity
Upper
00
Lower
01
No. of Data
02
Data
Upper
01
Lower
00
CRC
Upper
B3
Lower
CF
(Under voltage writing)
Write 2 Register
[10H]: With this instruction, the value of the action command (0001)
and the reference frequency (0002) can be modified simultaneously;
Notes:
You should set the operation control mode and frequency-setting mode as serial
communication at the same time.
Example: Start No.1 ac drive as clockwise operating, set the frequency as 50HZ.
(
Pb.05=0
)
Slave Address
01
Function Code
10
Starting
No.
Upper
00
Lower
01
Quantity
Upper
00
Lower
02
No. of Data
04
Data
Upper
00
Lower
01
Upper
13
Lower
88
CRC
Upper
6E
Lower
F5
Slave Address
01
Function Code
90
Error Code
03
CRC
Upper
0C
Lower
01
Slave Address
01
Function Code
10
Startin
g No.
Upper
00
Lower
01
Quant
ity
Upper
00
Lower
02
CRC
Upper
10
Lower
08
Command Message
Normal Response Message AbnomalResponse Message
Note:
No. of Data is double
Command Message
Quantity