Chapter 5 Parameter Introductions
http://www.acdrive-china.com
177
Note:
◆
Analog PID feedback/ feed is the Product of “percentage of physical value
corresponding to analog value” and “Analog closed loop measuring range”.
◆
If PC.15 is set to 1, analog PID feedback will be displayed in monitoring state, and all
unit indicators will be lit up. If it is set to 0, analog PID feedback will not be displayed.
◆
If PC.16 is set to 1, analog PID feed will be displayed in monitoring state, and all unit
indicators will lit up and flickered. If P7.00 is set to 0 and P7.01 is not set to 9, when
the user press shift key >> to monitor this object or Analog PID feedback, analog
PID feed can be adjusted online and be saved into P7.02 after press “ENTER” key.
PC.17 External counting value (no unit)
Range: 0,1
【
0
】
0: No display
1: Display
Note:
◆
If PC.17 is set to 1, external count value will be displayed in monitoring state, and all
unit indicators will be off. If it is set to 0, external count value will not be displayed.
PC.18 Terminal status (no unit)
Range: 0,1
【
0
】
0: No display
1: Display
Note:
◆
If PC.18 is set to 1, the terminal status will be displayed in monitoring state; If PC.18
is set to 0, the terminal status will not be displayed.
◆M
odel of 3004GB and the below models: The terminal information includes status of
terminal X1~X5, bi-direction open-collector output terminals D0 and relay output
terminal TA. The status of terminals is indicated by “on” or “off’ of the segment. The
segment will turn on if the terminal is valid. The segment will turn off if the terminal is
invalid. The central four segments are always on for the convenience of observation.
As shown in Fig.5-12-1:
◆M
odel of 35R5GB/37R5PB and above models: The terminal information includes
status of terminal X1~X8, bi-direction open-collector output terminals D0, Y1 and Y2,
and relay output terminal TA and BRA. The status of terminals is indicated by “on” or
“off’ of the segment. The segment will turn on if the terminal is valid. The segment
will turn off if the terminal is invalid. The central four segments are always on for the
convenience of observation. As shown in Fig.5-12-2:
X3
X5
X4
X2
X1
Relay
TA/TB/TC
DO
Always on
Fig. 5-12-1 Terminal status diagram of S2R4GB
~
3004GB