Figure 19 Inverter Installation on the Wall
Figure 20 Cable Box, Section View
Figure 21 Network Cable Type 568B&Wiring the Communication Cable
Step 10
Hang the inverter onto the mounting panels, adjust the entire system and
ensure that the battery and the inverter have been securely hung onto the panels and
brackets.
2.2.2 Inverter Installation
Step 11
Open the front cover and the cable box, and connect the Backup and Grid
cables to the Backup and Grid terminal board through the Backup and Grid wring outlet.
Step 12
Connect the meter communication cable, ethernet cable and the BMS commu-
nication cable to the corresponding COM ports. All of the three cables are regular net
cables, type 568B. You can use the communication cable provided in the accessory parts
of one SMILE5-BAT as the BMS communication cable.
The following figure shows the type 568B line sequence:
Step 13
Open the battery front covers. Connect the BMS communication cable of the
cable box from Step 11 to the topmost battery at the right side. Then use the BMS
communication cable supplied with the batteries to connect the batteries to each other
via the respective connectors on the left side. If more battery modules are to be added
you must mount them before connecting.
INSTALLATION
INSTALLATION
Note:
The front cover of the battery should not be opened more than 90°.
16
17