Operation
41
2. Function
When the start signal activates in stand-by mode, it starts the unit. (This includes preheating.) When the
stop signal activates, the unit will continue to operate for 10 seconds to cool down, then the unit stops
and is placed again in stand-by mode.
3. Starting Action
If the engine will not start after cranking for 10 seconds, stop it for 8 seconds before trying again. If the
engine will not start even after cranking is repeated three times, the SHUTDOWN lamp [I] will illuminate
due to “Fail to Start” error.
If the engine will not start and the Shutdown lamp is illuminated, troubleshoot the cause of engine failure
before proceeding.
Perform periodical inspection and maintenance of the generator
To check performance, run the unit for 5 to 10 minutes once in a week.
5 s
0-15 s
Protection circuit lagging 10 s