Three-Conductor Cable (Unit: in² (mm²))
Length
(ft (m)) /
Current
164
(50)
246
(75)
328
(100)
410
(125)
492
(150)
656
(200)
50A
0.02
(14)
0.02
(14)
0.03
(22)
0.03
(22)
0.05
(30)
0.06
(38)
100A
0.06
(38)
0.06
(38)
0.06
(38)
0.08
(50)
0.08
(50)
0.09
(60)
150A
0.03x2
(22x2)
0.03x2
(22x2)
0.06x2
(38x2)
0.06x2
(38x2)
0.06x2
(38x2)
0.08x2
(50x2)
Fuel Pipe Selector Valve
WARNING
• Monitor the fuel feeding conditions while feeding fuel
from a separate fuel storage tank.
• Do not switch the selector valve to the external tank
position unless an external tank is being used. Fuel
pipe damage and fuel leakage may result.
• Do not use excessive force operating the selector
valve handle. Valve damage and fuel leakage may
result.
This valve is designed to feed fuel to the engine from
an external fuel storage tank.
Operation
1. Unit is delivered from factory with fuel line piping and
selector valves set as shown (
A
). When operating the
unit using installed fuel tank, run the machine with the
fuel line piping and selector valves with the factory-
arranged settings.
2. When using a separate storage tank (
B
), remove the
plugs (
C
) fitted at the connections to the separator
tank and make piping connections as shown in
D
.
Then switch the selector valve handle as shown (
E
).
3. When removing the external tank, be sure to return
the selector valve handle to the original position (A),
remove the external tank piping connections, and
reinstall the plugs.
Installation of Separate Storage Fuel Tank and
Piping
1. Use oil resistant fuel hose with inside diameter of
8mm to 10mm.
2. Install the fuel tank so that the fuel level of the tank
may be kept at a level 0 - 98” (0 - 2.5m) higher than
the machine.
3. In order to avoid suction of water and sediment,
install the suction and return pipe so that the inlet
ports are 0.6 - 0.8” (15 - 20mm) higher than the
bottom of the tank (
B
).
4. When refilling fuel in the tank, be careful to not mix
water and sediment.
0.6 - 0.8”
(15 - 20mm)
Grounding
Min. 0”
(0m)
Max.
98”
(2.5m)
A
E
B
C
D
Summary of Contents for Maxi-Power MP65 T4F
Page 65: ...N o t f o r R e p r o d u c t i o n 65 Dimensions units in...
Page 66: ...N o t f o r R e p r o d u c t i o n 66 ALLMAND COM Dimensions units mm...
Page 67: ...N o t f o r R e p r o d u c t i o n 67 Generator Wiring Diagram...
Page 68: ...N o t f o r R e p r o d u c t i o n 68 ALLMAND COM Engine Wiring Diagram...
Page 69: ...N o t f o r R e p r o d u c t i o n 69 Connector Terminal Arrangement...
Page 74: ...N o t f o r R e p r o d u c t i o n 74 ALLMAND COM...