Rockwell Automation Publication 2097-UM001D-EN-P - November 2012
Chapter 6
Configure and Start Up the Kinetix 300 Drive
6.
Click the Date and Time tab.
7.
Check the box Make this controller the Coordinated System Time master.
8.
Click OK.
Configure the Ethernet Port
This section applies when the CompactLogix controller, catalog number 1769-
L23E-QB1, is used.
Follow these steps to configure the Ethernet port.
1.
Right-click the embedded
1769-L23E-QB1 Ethernet
port and choose Properties.
The Module Properties dialog box opens.
2.
Enter the IP address of the Ethernet port.
In this example, the IP address is 192.168.124.2. This is the controller
Ethernet address, not the drive Ethernet address.
3.
Click OK.
IMPORTANT
You can assign only one ControlLogix controller as the Coordinated
System Time master.