Publication 1756-UM522B-EN-P - February 2003
C-110 1756-DMF30 Specific Information
8
Bad FML Req
More than one incompatible Field operating mode is
requested at a time in parameter 166 [Motor Ctrl
Cmmd]. The following operating modes are mutually
exclusive:
••••
Field Alpha Test
••••
Field Identification Test
••••
Field Run
This bit is also set if you have attempted to restart the
drive without resetting the appropriate command bits
from parameter 166. Note that the bits in register 166
are edge-sensitive.
9
F Par NotLod
Field configuration parameters have not been
downloaded into the PMI module from the Dive
Module.
10
F Gns NotLod
Field configuration parameters have not been
downloaded into the PMI module from the Dive
Module.
11
F Flt Rst Rq
Previous field faults (parameter 2122 [MC Faults]),
e.g., field loss and line synchronization loss faults,
have not been cleared.
14
F FB or CFG
A field current feedback fault or configuration error
has occured:
••••
The drive has sensed field current feedback
when the field is off.
••••
You have attempted to turn on the field without
setting parameter 2200 [PMI Drive Config] bit
12 [Fld Reg Used].
Bit
Fault Name
Fault Description
Summary of Contents for ControlLogix 1756-DMD30
Page 1: ...ControlLogix Drive Module 1756 DMD30 1756 DMF30 User Manual y...
Page 4: ......
Page 8: ...Publication 1756 UM522B EN P February 2003 4...
Page 10: ...Publication 1756 UM522B EN P February 2003 Summary of Changes 2 Notes...
Page 14: ...Publication 1756 UM522B EN P February 2003 Preface 4 Notes...
Page 26: ...Publication 1756 UM522B EN P February 2003 2 4 Drive Comm Drive Communication Notes...
Page 44: ...Publication 1756 UM522B EN P February 2003 4 8 Installing the Drive Module Notes...
Page 252: ...Publication 1756 UM522B EN P February 2003 B 172 1756 DMD30 Specific Information Notes...