1756-DMD30 Specific Information B-43
154
Stop Dwell Time
Sets an adjustable delay time between detecting zero speed
and disabling the speed and torque regulators, when
responding to a stop command.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Sec
0
0
10
Linkable, Read-Write, Floating Point
Dynamic Control
Stop/Brake Modes
Drive Operation when paramter 154 [Stop Dwell Time] equals zero
Drive Operation when paramter 154 [Stop Dwell Time] is greater than zero
No.
Name
Description
Values
IMPORTANT
Consult industry and local codes when setting the value of this parameter.
P 160 [Zero Speed Lim]
Speed
Dr
iv
e Receiv
es Stop Command
0
Time
Dr
iv
e Detects Zero Speed
and
Tu
rns Off Regulators
When parameter 154 [Stop Dwell Time] equals
zero, the drive turns off the velocity and torque
regulators when it detects zero speed.
P 160 [Zero Speed Lim]
Speed
Dr
iv
e Receiv
es Stop Command
0
Time
Dr
iv
e Detects Zero Speed
Dr
iv
e
Tu
rns Off Regulators
P 154 [Stop Dwell Time]
When parameter 154 [Stop Dwell
Time] is greater than zero, the drive
delays turning off the velocity and
torque regulators for the amount of
time specified by parameter 154.
Summary of Contents for ControlLogix 1756-DMD30
Page 1: ...ControlLogix Drive Module 1756 DMD30 1756 DMF30 User Manual y...
Page 4: ......
Page 8: ...Publication 1756 UM522B EN P February 2003 4...
Page 10: ...Publication 1756 UM522B EN P February 2003 Summary of Changes 2 Notes...
Page 14: ...Publication 1756 UM522B EN P February 2003 Preface 4 Notes...
Page 26: ...Publication 1756 UM522B EN P February 2003 2 4 Drive Comm Drive Communication Notes...
Page 44: ...Publication 1756 UM522B EN P February 2003 4 8 Installing the Drive Module Notes...
Page 252: ...Publication 1756 UM522B EN P February 2003 B 172 1756 DMD30 Specific Information Notes...