DESCRIPTION
The dimensional drawing (see page 1-2) identifies various components of the
Alga
s-SDI
TORREXX
TM
SSR m
odel
vaporizer. This equipment is intended for
use with liquid propane, butane, or propane-butane mixtures. Multiple resistance
heating elements provide thermal energy to the finned aluminum heat exchanger.
A solid-state controller monitors the heat exchanger temperature and regulates
the operating temperature to a predetermined set point. The controls consist of 2
individual K-type thermocouple sensors with independent high temperature limits.
One sensor monitors operating temperature and the other controls the liquid inlet
solenoid valve. The liquid inlet solenoid valve does not open until a
predetermined warm-up temperature is reached. The vaporizer reaches
operating temperature in approximately 60 seconds from a cold start. The
vaporized LPG rises into the vapor header and exits through the vapor outlet.
The Liqui-SAFE
TM
Valve is designed to prevent liquid from passing downstream.
TORREXX
TM
Vaporizer can be configured for many applications.
♦
Standard configuration for Zone I for use with Propane and LPG, DNV GL
Nemko Presafe & CE mark. In this configuration the TORREXX
TM
complies
with the following standards:
o
EN 60079-0:2012/A11:2013 (IEC 60079-0 ed. 6.0)
o
EN 60079-1:2014 (IEC 60079-1 ed. 7.0)
o
EN 60079-18:2015 (IEC 60079-18 ed. 4.0)
♦
TORREXX
TM
vaporizer can be manifolded together for increased capacity on
a single skid. Consult Algas-SDI for Configuration information.
♦
TORREXX
TM
vaporizer can be packaged with an Algas-SDI mixing system
on a single skid. Consult Algas-SDI for Configuration information.
♦
For customizing the TORREXX
TM
vaporizer to your requirements consult
Algas-SDI for information.
Summary of Contents for TORREXX TX240
Page 52: ...APPENDIX A TECHNICAL INFORMATION ...
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 80: ...ASCO Valve used by Algas SDI ...
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......