ASDI
Operations and Maintenance – TX Models – P/N: 54629
6-32
TREE # 2B
Liqui-SAFE VALVE DOES NOT TRIP
GREEN
IS RELAY
LATCHED?
CHECK FUSE LINKS
FUSE LINKS
OPEN?
REPLACE OPEN
FUSE LINKS.
CONTACT ASDI
YES
NO
CHECK FOR LOOSE
WIRING
YES
NO
PRESS HI-LIMIT
BUTTON TO RESET
VAPORIZER
STARTS
WORKING?
CHECK:
1. IF THERMOCOUPLE
CONNECTION TO CONTROL
BOARD IS LOOSE
2. CHECK THERMAL GREASE
COATS LAST 2 INCHES OF
THERMOCOUPLE TIP WHEN
REMOVED FROM
THERMOWELL
3. CHECK THERMOCOUPLE IS
FULLY INSERTED IN THE
THERMOWELL. WHEN FULLY
INSERTED THERMOCOUPLE
SHOULD BOTTOM OUT IN THE
THERMOWELL AND
THERMOCOUPLE SHEATHING
SHOULD COMPRESS TO
SECURE BAYONETT FITTING
4. REMOVE DRAIN PLUG AND
CHECK FOR HEAVY ENDS
IF THE ABOVE ACTIONS DO
NOT FIX THE PROBLEM THEN
REPLACE TEMPERATURE
CONTROLLER BOARD.
CHECK IF THERE
IS 24V AT THE
RELAY LEADING
TO THE
TEMPERATURE
CONTROLLER
NO
YES
24V AT THE
RELAY?
YES
REPLACE RELAY
IS THERE A
LOOSE WIRE?
TIGHTEN WIRES.
RESTART
VAPORIZER.
SEE HEATER CORE
RESISTANCE ON
PAGE 6-37.
SERVICE INLET
SOLENOID WITH
SERVICING KIT (SEE
SPARE PARTS LIST).
NO
YES
NO
REPLACE
THERMOCOUPLE
Summary of Contents for TORREXX TX240
Page 52: ...APPENDIX A TECHNICAL INFORMATION ...
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 80: ...ASCO Valve used by Algas SDI ...
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......