5-25
ASDI
Operations and Maintenance – TX Models – P/N: 54629
Liqui–SAFE Valve – Service Instructions
There are four (4) o-rings in the Liqui-SAFE
TM
valve; the button post O-ring, valve
body O-ring, valve seat O-ring and valve stem base O-ring. Follow the
instructions below to service the Liqui-SAFE
TM
valve. Clean all the metal parts
with WD-40. Re-assemble all the parts. Simulate the tripping action of the valve
to ensure proper latch operation before re-installing in the vaporizer. The tripping
force applied on the Extension Stem is between 0.25 lbf (1.11 N) and 0.5 lbf
(2.22 N).
Figure 11A – STEP 1 – Be sure the Liqui-SAFE valve is in the closed position as shown.
Figure 11B – STEP 2 – Unscrew reset button base and remove the spring.
UNSCREW RESET
BUTTON BASE
REMOVE SPRING