Operations and Maintenance – TX Models – P/N: 54629
TREE # 1 A
Liqui-SAFE VALVE TRIPS
IS VAPORIZER WARM
AND UP TO
TEMPERATURE?
YES
NO
PERFORM FULL LOAD CURRENT CHECK.
SEE PAGE 6-36
SEE TROUBLESHOOTING
TREE 1B
IS CURRENT
CHECK GOOD?
YES
NO
PERFORM FULL LOAD VOLTAGE CHECK.
SEE PAGE 6-35
YES
NO
FIX VOLTAGE ISSUE
AND RESTART
VAPORIZER
IS VOLTAGE
CHECK GOOD?
CHECK FOR OPEN FUSE
LINKS
REMOVE LIQUI-SAFE VALVE. SEE PAGE
5-26
FOR SERVICE INSTRUCTIONS.
RE-INSTALL LIQUI-SAFE VALVE
RESTART
VAPORIZER.
DOES THE
VALVE TRIP?
YES
NO
VERIFY LOAD IS NOT
EXCEEDING THE
SYSTEM CAPACITY
VERIFY LIQUID LINE IS
SIZED CORRECTLY
FOR SYSTEM LOAD.
ENSURE THERE ARE
NO RESTRICTIONS IN
LIQUID LINES SUCH AS
PARTIALLY OPENED
VALVES OR A CHECK
VALVE. RESTRICTIONS
CAN BE IDENTIFIED BY
FROSTING ON THE
OUTSIDE OF THE PIPE.
RESUME OPERATING
THE VAPORIZER
FUSE LINKS
OPEN?
CHECK FOR OPEN
HEATERS.
CONTACT ASDI
REPLACE OPEN FUSE
LINKS.
CONTACT ASDI
NO
YES