ASDI
Operations and Maintenance – TX Models – P/N: 54629
2-6
MAJOR COMPONENTS
2
The TORREXX
TM
is designed to be reliable and user friendly. Several features
allow you to quickly determine the status of your vaporizer.
There are two basic control systems within a TORREXX
TM
:
1)
Heating System – Figure 2
2)
Liquid Passage Prevention System – Figure 3
Figure 2 – Heating System
TX320 SSR SHOWN
•
SELF REGULATING HEATING SYSTEM
•
NO START/STOP SWITCHES
•
ENGAGES AUTOMATICALLY
•
JUST APPLY POWER TO TURN VAPORIZER ON
POWER DISTRIBUTION BLOCK
UNUSED
ENTRY /
CUSTOMER
ELECTRICAL
CONNECTION
(M32 X 1.5)
SOLID-STATE
RELAYS
TEMPERATURE CONTROLLER
DETECTS HEAT EXCHANGER
TEMPERATURE VIA DUAL K TYPE
THERMOCOUPLE
TEMPERATURE ACTIVATED
CIRCUIT OPENS AT 55
°
C OR
131
°
F WITH SOLENOID VALVE
TO ENSURE AUTOMATIC
RESTART AFTER POWER
INTERRUPTION