6-39
ASDI
Operations and Maintenance – TX Models – P/N: 54629
Solenoid Valve Electrical Test
NOTE
A multimeter is required for the following test.
CAUTION
Turn off electrical power at the disconnect before performing this
procedure.
Open the electrical housing at the vaporizer base. Disconnect the 2-PIN Molex
plug connector and measure resistance between the pins. You should measure
approximately 3 Ohms. If not, replace the solenoid coil.
Figure 16 – Solenoid Valve Electrical Test
RESISTANCE SHOULD BE
APPROXIMATELY 3 OHMS
DISCONNECT
MOLEX JUMPER
CONTROL
BOARD