Installing PSUs
7750 SR-a4 and SR-a8 Installation Guide
105
Required tools and hardware
•
three lengths of #8 AWG wire: one length for the ground and two lengths for the
battery cables, prepared as described in
Preparing the PSU Ground and Power Cables
•
Phillips torque screwdriver
To connect the –48 VDC power feeds:
Step 1.
Ensure that all power to the router at the remote DC power source is OFF.
Step 2.
Attach the ground wire, if required by the local electrical code.
i.
Run a length of ground wire from the appropriate grounding point to the router.
ii. Prepare the end of the wire at the ground point according to local safety
practices and attach it to the grounding terminal.
iii. Prepare the end of the wire at the router by attaching a ring lug, as described in
Preparing the PSU Ground and Power Cables on page 101
.
iv. Attach the ring lug on the ground wire to the DC PSU ground (Key 1 in
v. Tighten the M4 screw. Do not over-tighten. Torque to 8-10 lbf-in.
Step 3.
Remove the safety cover from the three raised guides on the terminal block (Key4
in
Step 4.
Remove the positive and negative terminal screws (Keys 2 and 3 in
).
Step 5.
Make the battery return connections.
i.
Run the length of wire from the power source positive terminal to the terminal
block on the router.
ii. Prepare the end of the wire at the power source according to local safety
practices and attach it to the power source positive terminal.
iii. Prepare the end of the wire at the router by attaching a ring lug, as described in
Preparing the PSU Ground and Power Cables on page 101
.
iv. Attach the wire at the router end to the positive (+) battery return terminal on
the PSU.
v. Replace and tighten the terminal screw using a Phillips torque screwdriver. Do
not over-tighten. The recommended torque is 3 lbf-in (0.339 N
.
m).
Step 6.
Make the battery connections to the disconnect device.
i.
Run a length of wire from the disconnect device to the router.
ii. Prepare the end of the wire at the router by attaching a ring lug, as described in
Preparing the PSU Ground and Power Cables on page 101
.
iii. Attach the battery wire at the router end to the negative (–) battery terminal on
the PSU.
Summary of Contents for 7750 SR-a4
Page 8: ...Table of Contents 8 7750 SR a4 and SR a8 Installation Guide...
Page 12: ...List of Tables 12 7750 SR a4 and SR a8 Installation Guide...
Page 16: ...List of Figures 16 7750 SR a4 and SR a8 Installation Guide...
Page 22: ...Technical Support 22 7750 SR a4 and SR a8 Installation Guide...
Page 70: ...Safety Standards Compliance Agency Certifications 70 7750 SR a4 and SR a8 Installation Guide...
Page 136: ...Troubleshooting Initial Startup 136 7750 SR a4 and SR a8 Installation Guide...
Page 170: ...44 port 1GigE CSFP SFP MDA a Overview 170 7750 SR a4 and SR a8 Installation Guide...
Page 210: ...Removing and Replacing an Impedance Panel 210 7750 SR a4 and SR a8 Installation Guide...
Page 232: ...2015 Alcatel Lucent All rights reserved 3HE 10231 AAAA TQZZA Edition 01...