Installing PSUs
7750 SR-a4 and SR-a8 Installation Guide
103
To prepare the PSU end of the DC power cables:
Step 1.
For the DC positive and DC negative wires, use a wire-stripping tool to strip the
wire insulation to the length according to the recommendation of the manufacturer
or local safety code (Keys 1 and 2 in
Step 2.
Attach each wire to the terminal ring and crimp the ring lug according to the
instructions of the terminal ring manufacturer (Key 3 in
).
Figure 33: Attaching the Ring Lug to a Power Cable
Remote Cable Connections
Cables that connect to the building ground point, equipment bus ground point, DC power
sources, and disconnect devices must be prepared and attached according to the local safety
code.
shows an example of how redundant connections can be terminated. A circuit
breaker is used in each power feed as a disconnect device. See
for information about the recommended ratings for circuit breakers.
Table 45: Ring Lug to Power Cable Descriptions
Key
Description
1
#8 AWG copper wire (see Required tools and hardware)
2
Insulation stripped according to the recommendation of the manufacturer or local
safety code
3
Ring lug (see Required tools and hardware)
3
2
1
19641
Summary of Contents for 7750 SR-a4
Page 8: ...Table of Contents 8 7750 SR a4 and SR a8 Installation Guide...
Page 12: ...List of Tables 12 7750 SR a4 and SR a8 Installation Guide...
Page 16: ...List of Figures 16 7750 SR a4 and SR a8 Installation Guide...
Page 22: ...Technical Support 22 7750 SR a4 and SR a8 Installation Guide...
Page 70: ...Safety Standards Compliance Agency Certifications 70 7750 SR a4 and SR a8 Installation Guide...
Page 136: ...Troubleshooting Initial Startup 136 7750 SR a4 and SR a8 Installation Guide...
Page 170: ...44 port 1GigE CSFP SFP MDA a Overview 170 7750 SR a4 and SR a8 Installation Guide...
Page 210: ...Removing and Replacing an Impedance Panel 210 7750 SR a4 and SR a8 Installation Guide...
Page 232: ...2015 Alcatel Lucent All rights reserved 3HE 10231 AAAA TQZZA Edition 01...