Installing, Wiring, and Connecting a –48 VDC PSU
102
7750 SR-a4 and SR-a8 Installation Guide
•
three lengths of #8 AWG wire, insulated and color-coded according to local safety
code, or #8 AWG jacketed three-conductor cord:
→
one ground wire, measured to extend from the PSU to the building ground point
or equipment bus ground point
→
one positive battery cable, measured to extend from the PSU to the positive
battery terminal
→
one negative battery cable, measured to extend from the PSU to the negative
battery terminal or disconnect device, if used
•
three single-hole terminal lugs for the three lengths of #8 AWG wire for connection
to the PSU
•
wire stripping tool
•
wire crimper
•
Phillips torque screwdriver
To prepare the PSU end of the ground cable:
Step 1.
Using a wire-stripping tool, strip the wire insulation to the length according to the
recommendation of the terminal manufacturer or local safety code (Keys 1and 2 in
Step 2.
Attach the wire to the terminal ring and crimp the ring lug according to the
instructions of the terminal ring manufacturer (Key 3 in
).
Figure 32: Attaching the Ring Lug to a Ground Cable
Table 44: Ring Lug to Ground Cable Descriptions
Key
Description
1
#8 AWG copper wire (see Required tools and hardware)
2
Insulation stripped according to the recommendation of the manufacturer or local
safety code
3
Ring lug (see Required tools and hardware)
3
2
1
19641
Summary of Contents for 7750 SR-a4
Page 8: ...Table of Contents 8 7750 SR a4 and SR a8 Installation Guide...
Page 12: ...List of Tables 12 7750 SR a4 and SR a8 Installation Guide...
Page 16: ...List of Figures 16 7750 SR a4 and SR a8 Installation Guide...
Page 22: ...Technical Support 22 7750 SR a4 and SR a8 Installation Guide...
Page 70: ...Safety Standards Compliance Agency Certifications 70 7750 SR a4 and SR a8 Installation Guide...
Page 136: ...Troubleshooting Initial Startup 136 7750 SR a4 and SR a8 Installation Guide...
Page 170: ...44 port 1GigE CSFP SFP MDA a Overview 170 7750 SR a4 and SR a8 Installation Guide...
Page 210: ...Removing and Replacing an Impedance Panel 210 7750 SR a4 and SR a8 Installation Guide...
Page 232: ...2015 Alcatel Lucent All rights reserved 3HE 10231 AAAA TQZZA Edition 01...