g. When the wires have been connected, place the back cover of the plastic
panel, bring the plastic panel to its initial position and place the front case
panel of the boiler back.
OTS= Outside Temperature Sensor
RT= Room Thermostat
Figure 19.
Interior view of the plastic panel
4.9 Flue Connection
In order to ensure that the appliance functions correctly and efficiently,
the flue connection between the boiler and the flue terminal must be
made using original components specifically designed for condensing
boilers.
Traditional flue components cannot be used for conveying exhaust
fumes from condensing boilers, nor vice versa.
• Below suggestions must be taken into consideration for flue installation:
- Horizontal air intake pipes must slope downwards by 3° at the wall towards
atmosphere to prevent the entry of rain water, dust or impurities to the pipe.
For horizontal flue gas pipes, situation is different. Flue gas pipes must
slope upwards by 3° to facilitate the flow of condensate water in flue back
to combustion chamber, to prevent the stalactite formation by freezing in
winter and the risk of drop and hurting to walking people (Figure 20). In case
of horizontal concentric flues, flue gas pipe (inner pipe) must slope upwards
whereas air intake pipe (outer pipe) must slope downwards. Horizontal
concentric flue set must be installed parallel to floor. After installation
horizontally, flue gas pipe stands slopped upwards by itself as a result of
special design (Figure 21).
DETAIL - A
Summary of Contents for SUPER FIT 24
Page 2: ...Code No A 1 5 1i Publishing Date 020321 Revision Date 020321...
Page 8: ...8 1 2 Declaration of Conformity...
Page 23: ...23 3 TECHNICAL CHARACTERISTICS 3 1 Technical Data...
Page 26: ...26 3 4 Dimensions 3 4 Dimensions Figure 7 Dimensions Figure 7 Dimensions Gas Inlet...
Page 35: ...35 Opening the Package Opening the Package Figure 13 Opening the package...
Page 46: ...46 Figure 24 Flue applications...
Page 52: ...52...
Page 53: ...53...
Page 54: ...54...
Page 55: ...55...