Suburban DynaPack S & H Series Owner's Manual 06/2020 Rev.2 

6

  E:  INSTALLING AND SECURING UNIT TO WALL SLEEVE

SELF-DRILLING SCREW

STRAP

LEG LEVELER

3

8 -16 JAM NUT

THE LEG LEVELERS INSTALL INTO

A WELD NUT ATTACHED TO THE 

UNDERSIDE OF THE DRAIN PAN.

ONCE THE UNIT IS LEVEL, TIGHTEN

THE JAM NUT TO LOCK THE LEG 

LEVELER IN PLACE.

LEG LEVELER

WELD NUT

DRAIN PAN

JAM NUT

TRIM OFF EXCESS

STRAP MATERIAL

BEND STRAP AROUND

FRONT OF UNIT AND

SECURE WITH A SELF-

DRILLING SCREW

ENGAGE FLANGE ON WALL SLEEVE

WITH FLANGE ON STRAP.  SECURE

TO UNIT WITH SELF-DRILLING SCREWS.

Figure 4

 

Before installing and securing the unit to the wall sleeve, make sure that the 

proper grille kit is installed. Due to the temperatures of the combustion products 

released from the gas vent, DynaPack gas package units require the use of an 

aluminum grille kit (see the Accessories chapter).

1. 

Double check the installation of the wall sleeve to make sure it is securely 

attached to the wall opening. Inspect the wall sleeve drain for proper 

installation if an inside drain is being used. 

2. 

Examine the gaskets on the wall sleeve to make sure there is a continuous 

seal between the wall sleeve and the unit.

3. 

Place DynaPack unit onto the wall sleeve. Lift the unit 3/4" and place 

over the wall sleeve base (see Figure 4). A PALLET JACK works well for 

this. Temporarily block the unit up and install front leveling bracket (see 

Figure 4). Adjust leveling legs to level.

4. Use the two retaining straps to secure the unit to the wall sleeve (see 

Figure 4). Verify that the gaskets of the wall sleeve make a complete seal 

to the unit paying particular attention to top and bottom corners of the unit 

to sleeve seal. Caulk if needed.

  F:  DUCT WORK  

The duct work for the dwelling should be designed for the lowest possible 

static pressure to reduce energy usage and noise. Table 9 at the end of this 

chapter lists the approximate cfm delivery of the units on each of the indoor 

blower speeds. Table 4 lists the recommended heating and cooling speeds 

with its approximate cfm delivery. Use both tables to properly design the duct 

system for both heating and cooling cfm.

Note:

 Follow local codes and standards when designing duct runs to deliver 

the required airflow. Minimize noise and excessive pressure drops caused by duct aspect ratio changes, bends, dampers and outlet 

grilles in duct runs.

Model

Recommended

Heating Speed

Approx.

CFM

Approx.

Temp Rise F

Recommended

Cooling Speed

Approx.

CFM

DYPA12AC3A036

medium

700

38

Low

400

DYPA12AC3A048

medium

700

50

Low

400

DYPA18AC3A036

medium

700

38

medium low

550

DYPA18AC3A048

medium

700

50

medium low

550

DYPA18AC3A060

medium high

900

50

medium low

550

DYPA24AC3A036

medium

700

38

medium

700

DYPA24AC3A048

medium high

900

40

medium

700

DYPA24AC3A060

medium high

900

50

medium

700

DYPA30AC3A036

medium

700

38

medium high

900

DYPA30AC3A048

medium high

900

40

medium high

900

DYPA30AC3A060

medium high

900

50

medium high

900

Table 2

  G:  CONDENSATE DRAIN 

RETURN

SUPPLY

ACCESS PANEL 

TO 

CONTROLS

ACCESS PANEL 

TO GAS VALVE 

AND BURNERS

ACCESS PANEL 

TO COMPRESSOR 

AND OUTDOOR FAN

DRIP LEG (FIELD SUPPLIED)

MANUAL SHUTOFF VALVE 

WITH 

1

8

"NPT PLUGGED TAPPING,

ACCESSIBLE FOR TEST GAUGE

CONNECTION (FIELD SUPPLIED)

CONDENSATE DRAIN

GROUND JOINT UNION

(FIELD SUPPLIED)

FILTER DOOR

TRAP

ROUTE TO BUILDING DRAIN

ELECTRICAL POWER ENTRANCE

FRONT VIEW

Figure 5

The Dynapack unit and wall sleeve each have there own drain. The unit drain is for the 

condensate developed by the evaporator coil. It needs to be trapped and routed to the 

building drain system. Use ¾” pvc pipe and fittings (field supplied). 
The wall sleeve is equipped with a drain pan that collects rain water entering the wall 

sleeve and the unit condenser coil area. At the time of installation of the wall sleeve, this 

drain can be directed directly outside or turned inside and routed to the building drain 

system. If the wall sleeve drain is routed to the building sewer system then it must be 

trapped to prevent sewer gasses from escaping.

Summary of Contents for Suburban DynaPack H Series

Page 1: ...m WARNING If the information in these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other...

Page 2: ...and cooling system that provides designers and builders with a cost effective alternative to condition multiple rooms in a multi unit housing application The DynaPack features 1 to 2 5 Tons Cooling 36...

Page 3: ...R CC BK BK BK 24 VAC GROUND Y W C R G PK HUM FLAME 24V FLAME SWITCH BL O 230V INDUCER BK R OFM C BK BR WHT GAS VALVE SWITCH HIGH LIMIT ROLLOUT SWITCH SWITCH PRESSURE O BL PK PK R O G BL Y BL BL BL O N...

Page 4: ...units are vertical package units featuring gas fired heating with electrical air conditioning The Dynapack unit has been safety certified by Intertek Testing Services to comply with the national safet...

Page 5: ...in any manner other than what is specified in these instructions The installation must be planned before hand so that the unit exhaust vent location complies with local or national codes in regards t...

Page 6: ...of the units on each of the indoor blower speeds Table 4 lists the recommended heating and cooling speeds with its approximate cfm delivery Use both tables to properly design the duct system for both...

Page 7: ...es to comply with the national safety codes of the USA and Canada The Dynapack unit is certified to operate on natural gas The Dynapack unit is NOT certified for installation in a mobile home Installa...

Page 8: ...ed certain distances from adjacent doors operable windows and shrubbery See figure 11 at the end of this chapter CAUTION The unit must be installed level front to back and side to side Adjust front le...

Page 9: ...1738 10 11 7 8 35 14 1744 1739 12 13 7 8 37 16 1745 1740 14 15 7 8 39 18 1769 1770 16 17 7 8 41 20 1771 1772 17 18 7 8 42 21 1773 1774 18 19 7 8 43 22 20 21 7 8 45 24 22 23 7 8 47 26 Table 4 E INSTALL...

Page 10: ...he building drain system Use pvc pipe and fittings field supplied The wall sleeve is equipped with a drain pan that collects rain water entering the wall sleeve and the unit condenser coil area At the...

Page 11: ...ing system during testing Once the gas piping up to the shut off valve has been tested the remaining piping to the unit gas valve must be tested Do not exceed psig or 14 water column for this test or...

Page 12: ...ase the phase wire should be connected to L1 on the contactor An additional wire for unit grounding is required On 208 volt systems the transformer wiring needs to be changed Swap the red transformer...

Page 13: ...TO WINDOW OR DOOR THAT MAY BE OPENED 6 INCHES 15cm FOR APPLIANCES 10 000 Btuh 3kw 12 INCHES 30cm FOR APPLIANCES 10 000 Btuh 3kw AND 100 000 btuh 30kw CANADIAN INSTALLATIONS US INSTALLATIONS 1 2 6 INC...

Page 14: ...back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time of completion of installation the owner shall have a perio...

Page 15: ...to run and the compressor will start Note There will be a 5 minute delay in the compressor starting if the thermostat set point was raised and then lowered again 12 Once the room reaches the set temp...

Page 16: ...r conditioning performance If it is suspected that there is a refrigerant leak in the unit then the charge can be checked by placing a thermometer on the liquid line near the filter dryer and connecti...

Page 17: ...er obstructions Clean the condensate drain and ensure there are no obstructions On DYPA12 models place a thermometer on the compressor suction line above the accumulator Connect a pressure gauge to th...

Page 18: ...14 3 4 32 5 8 28 9 16 32 3 4 DYPA30AC3A 1741 5 7 8 6 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A and DYPA24AC3A 1742 7 7 8 8 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A and DYPA24AC3A 1743 9...

Page 19: ...ted service labor diagnosis calls filter driers refrigerant or any other material charges 2 Damages caused by shipping accident abuse negligence misuse fire flood or Acts of God 3 Damages caused by op...

Page 20: ...existing wires up to Top Line side of contactor 7 Wire as per drawing ES48000 sent with the kit to contactor ground lug 8 Re insert rubber drain hose through bushing with supplied Wires Heat cable 9 I...

Page 21: ...ent un incendie ou une explosion pourrait en r sulter entra nant des dommages mat riels des blessures corporelles ou m me la mort Ne pas entreposer ni utiliser d essence ou d autres vapeurs ou liquide...

Page 22: ...concepteurs et aux constructeurs une alternative conomique pour climatiser plusieurs pi ces dans un complexe d habitation Le DynaPack comporte 1 0 2 5 tonnes de refroidissement 36 60 MBTU de chauffag...

Page 23: ...BK BK 24 V Ca TERRE Y W C R G PK HUM FLAMME 24V INTERRUPTEUR DE FLAMME BL O 230V INDUCTEUR BK R OFM C BK BR WHT ROBINET GAZ INTERRUPTEUR FIN DE COURSE INTERRUPTEUR ROTATIF PRESSOSTAT O BL PK PK R O G...

Page 24: ...ynapack est une unit verticale comprenant un chauffage au gaz avec climatisation lectrique La s curit du Dynapack a t certifi e par Intertek Testing Services conform ment aux codes de s curit nationau...

Page 25: ...d une mani re quelconque autre que celle qui est sp cifi e dans ces instructions L installation doit tre planifi e l avance afin que l emplacement de l vent de l appareil soit conforme aux codes loca...

Page 26: ...e Approx CFM Approx Hausse Temp F Vitesse de refroidissement recommand e Approx CFM DYPA12AC3A036 moyenne 700 38 Bas 400 DYPA12AC3A048 moyenne 700 50 Bas 400 DYPA18AC3A036 moyenne 700 38 moyenne basse...

Page 27: ...t aux codes de s curit nationaux des tats Unis et du Canada Le Dynapack est certifi pour fonctionner au gaz naturel Le Dynapack n est PAS certifi pour installation dans une maison mobile Les installat...

Page 28: ...des buissons Voir la figure 11 la fin de ce chapitre MISE EN GARDE L appareil doit tre install niveau de l avant l arri re et de c t c t Ajustez les pieds de nivellement avant selon besoin B INSTALLAT...

Page 29: ...7 8 31 10 1742 1737 8 9 7 8 33 12 1743 1738 10 11 7 8 35 14 1744 1739 12 13 7 8 37 16 1745 1740 14 15 7 8 39 18 1769 1770 16 17 7 8 41 20 1771 1772 17 18 7 8 42 21 1773 1774 18 19 7 8 43 22 20 21 7 8...

Page 30: ...syst me de drainage du b timent Utilisez des tuyaux de et des raccords en PVC fournis par l installateur Le caisson mural est quip d un bac de r cup ration des eaux de pluie qui p n trent dans le cai...

Page 31: ...ssion d essai de la tuyauterie de gaz Sinon de la vanne de fermeture doit tre retir e du syst me de tuyauterie pendant les tests Une fois que la tuyauterie de gaz a t test e jusqu la vanne de fermetur...

Page 32: ...e est de 208 230 volts phase neutre Dans ce cas le fil de phase doit tre connect L1 sur le contacteur Un fil suppl mentaire pour la mise la terre de l appareil est requis Sur les syst mes 208 volts le...

Page 33: ...LES APPAREILS 50 000 Btuh 15 kW 6 POUCES 15cm POUR LES APPAREILS 10 000 Btuh 3 kW 9 POUCES 23 cm POUR LES APPAREILS 10 000 Btuh 3 kW ET 50 000 Btuh 15 kW 12 POUCES 30 cm POUR LES APPAREILS 50 000 Btuh...

Page 34: ...u prochain tage adjacent b Si les exigences de la pr sente sous section ne peuvent tre satisfaites au moment de l installation le propri taire dispose d un d lai de trente 30 jours pour se conformer a...

Page 35: ...le compresseur se met en marche Remarque il y aura un d lai de 5 minutes au d marrage du compresseur si le point de consigne du thermostat a t lev puis nouveau abaiss 12 Une fois que la pi ce a attei...

Page 36: ...ME L unit a t test e en usine pour assurer des performances appropri es de la climatisation Si l on soup onne une fuite de r frig rant dans l appareil la charge peut tre v rifi e en pla ant un thermom...

Page 37: ...at et assurez vous qu il n y a pas d obstruction Sur les mod les DYPA12 placez un thermom tre sur la conduite d aspiration du compresseur au dessus de l accumulateur Connectez un manom tre au port de...

Page 38: ...14 3 4 32 5 8 28 9 16 32 3 4 DYPA30AC3A 1741 5 7 8 6 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A et DYPA24AC3A 1742 7 7 8 8 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A et DYPA24AC3A 1743 9 7 8...

Page 39: ...ande l ex cution au titre de cette Garantie doit fournir un acc s raisonnable au produit ou la pi ce pr tendument d fectueux ou d faillant Airxcel Commercial Group et ses agents et employ s autoris s...

Page 40: ...t sup rieur ligne du contacteur 7 C blez selon le plan ES48000 envoy avec le kit au contacteur et la cosse de terre 8 R ins rez le tuyau de drainage en caoutchouc dans la bague avec les fils c ble de...

Reviews: