 13 

 

Suburban DynaPack S & H Series Owner's Manual 06/2020 Rev.2

INDOOR CFM vs STATIC PRESSURE (Dry coil + no air filter)

Model Number Blower 

Speed 0.10" wc 0.15" wc 0.20" wc 0.25" wc 0.30" wc 0.40" wc 0.50" wc 0.60" wc 0.70" wc 0.80" wc

DYPA12AC3A***

LO

497

473

448

424

400

348

296

247

212

160

MED LO

577

562

547

522

497

458

415

357

317

281

MED

757

748

739

716

692

670

635

586

558

521

MED HI

937

920

905

888

872

852

827

790

728

677

HI

1060

1050

1042

1015

977

927

876

824

758

700

DYPA18AC3A***

LO

512

491

469

428

387

320

285

250

213

179

MED LO

596

568

540

522

504

447

415

381

324

291

MED

773

761

748

730

711

675

640

622

586

550

MED HI

972

955

938

927

915

874

850

825

796

766

HI

1108

1091

1074

1057

1039

1002

970

917

868

796

DYPA24AC3A***

LO

504

483

461

420

379

312

252

207

N/R

N/R

MED LO

588

560

532

514

496

439

377

320

262

202

MED

765

753

740

722

703

667

622

572

532

482

MED HI

964

947

930

919

907

866

828

782

757

702

HI

1100

1083

1066

1049

1031

994

962

922

882

827

DYPA30AC3A***

LO

490

465

440

415

385

310

225

170

N/R

N/R

MED LO

570

540

520

500

476

415

365

310

250

205

MED

768

755

741

732

704

666

621

580

535

500

MED HI

934

922

913

895

873

835

800

760

730

690

HI

1064

1046

1017

1009

995

965

935

900

875

828

Table 9

VENT TERMINAL

AIR SUPPLY INLET

X

AREA WHERE TERMINAL IS NOT PERMITTED

A=

CLEARANCE ABOVE GRADE, 

VERANDA, PORCH, DECK, OR 

BALCONY

12 INCHES (30cm)

(SEE NOTE a)

12 INCHES (30cm)

(SEE NOTE a)

J=

CLEARANCE TO NONMECHANICAL 

AIR SUPPLY INLET TO BUILDING 

OR THE COMBUSTION AIR INLET 

TO ANY OTHER APPLIANCE.

CANADIAN INSTALLATIONS

US INSTALLATIONS

1

2

6 INCHES (15cm) FOR 

APPLIANCES £10,000 Btuh (3kw), 

12 INCHES (30cm) FOR 

APPLIANCES >

 

10,000 Btuh (3kw) 

AND  £

 

100,000 btuh (30kw)

6 INCHES (15cm) FOR APPLIANCES 

£10,000 Btuh (3kw), 

9 INCHES (23cm) FOR APPLIANCES 

>

 

10,000 Btuh (3kw) AND £

 

50,000 

Btuh (15kw)

12 INCHES (30CM) FOR 

APPLIANCES > 50,000 Btuh (15kw)

 

B=

CLEARANCE TO WINDOW OR 

DOOR THAT MAY BE OPENED

6 INCHES (15cm) FOR 

APPLIANCES £10,000 Btuh (3kw), 

12 INCHES (30cm) FOR 

APPLIANCES >

 

10,000 Btuh (3kw) 

AND  £

 

100,000 btuh (30kw)

CANADIAN INSTALLATIONS

US INSTALLATIONS

1

2

6 INCHES (15cm) FOR APPLIANCES 

£10,000 

Btuh (3kw), 

9 INCHES (23cm) FOR APPLIANCES 

>

 

10,000 Btuh (3kw) AND 

£

 

50,000 

btuh (15kw)

12 INCHES (30CM) FOR APPLIANCES 

50,000 Btuh (15kw)

K=

CLEARANCE TO A MECHANICAL 

AIR SUPPLY INLET

6 FEET (1.83m)

3 FEET (91cm) ABOVE IF WITHIN 10FEET 

(3m) HORIZONTALLY

C=

CLEARANCE TO WINDOW OR 

DOOR THAT MAY BE OPENED

* a

* a

L=

CLEARANCE ABOVE PAVED 

SIDEWALK OR PAVED DRIVEWAY 

LOCATIED ON PUBLIC PROPERTY

7 FEET (2.13m) 

* a

D=

VERTICAL CLEARANCE TO 

VENTILATED SOFFIT LOCATED 

ABOVE THE TERMINAL WITHIN A 

HORIZONTAL DISTANCE OF 2 FEET 

(61cm) FROM THE CENTER LINE 

OF THE TERMINAL

* a

* a

M=

CLEARANCE UNDER VERANDA, 

PORCH, DECK, OR BALCONY

12 INCHES (30cm) 

* a

E=

CLEARANCE TO UNVENTILATED SOFFIT

* a

* a

F=

CLEARANCE TO OUTSIDE CORNER

* a

* a

G=

CLEARANCE TO INSIDE CORNER

* a

* a

H=

CLEARANCE TO EACH SIDE OF 

CENTER LINE EXTENDED ABOVE 

METER / REGULATOR ASSEMBLY

3 FEET (91cm) WITHIN A HEIGHT 15 FEET 

(4.5m) ABOVE THE METER / REGULATOR 

ASSEMBLY

* a

I=

CLEARANCE TO SERVICE 

REGULATOR VENT OUTLET

3 FEET (91cm)

* a

1

IN ACCORDANCE WITH THE CURRENT CSA B149.1, NATURAL GAS AND PROPANE INSTALLATION CODE

2

IN ACCORDANCE WITH THE CURRENT ANSI Z223.1/NFPA 54, NATIONAL FUEL GAS CODE

A VENT SHALL NOT TERMINATE DIRECTL ABOVE A SIDEWALK OR PAVED DRIVEWAY THT IS LOCATED BETWEEN TWO SINGLE 

FAMILY DWELLINGS AND SERVES BOTH DWELLINGS
PERMITTED ONLY IF VERANDA, PORCH, DECK, OR BALCONY IS FULLY OPEN ON A MINUMUM OF TWO SIDES 

BENEATH THE FLOOR.
FOR CLEARANCES NOT SPECIFIED IN ANSI Z223.1/NFPA 54 OR CSA B149.1, ONE OF THE FOLLOWING SHALL BE 

INDICATED:

*

A REFERENCE TO THE FOLLOWING FOOTNOTE:

"CLEARANCE IN ACCORDANCE WITH LOCAL INSTALLATION CODES AND THE REQUIREMENTS OF THE GAS SUPPLIER AND 

MANUFACTURERS INSTALLATION INSTRUCTIONS (SEE MANUAL SUPPLIED WITH APPLIANCE)

a)

OPERABLE

FIXED 

CLOSED

FIXED 

CLOSED

INSIDE

CORNER DET

AIL

G

OPERABLE

A

C

F

B

B

B

B

A

J

B

I

H

M

K

E

D

L

B

Figure 11

Summary of Contents for Suburban DynaPack H Series

Page 1: ...m WARNING If the information in these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other...

Page 2: ...and cooling system that provides designers and builders with a cost effective alternative to condition multiple rooms in a multi unit housing application The DynaPack features 1 to 2 5 Tons Cooling 36...

Page 3: ...R CC BK BK BK 24 VAC GROUND Y W C R G PK HUM FLAME 24V FLAME SWITCH BL O 230V INDUCER BK R OFM C BK BR WHT GAS VALVE SWITCH HIGH LIMIT ROLLOUT SWITCH SWITCH PRESSURE O BL PK PK R O G BL Y BL BL BL O N...

Page 4: ...units are vertical package units featuring gas fired heating with electrical air conditioning The Dynapack unit has been safety certified by Intertek Testing Services to comply with the national safet...

Page 5: ...in any manner other than what is specified in these instructions The installation must be planned before hand so that the unit exhaust vent location complies with local or national codes in regards t...

Page 6: ...of the units on each of the indoor blower speeds Table 4 lists the recommended heating and cooling speeds with its approximate cfm delivery Use both tables to properly design the duct system for both...

Page 7: ...es to comply with the national safety codes of the USA and Canada The Dynapack unit is certified to operate on natural gas The Dynapack unit is NOT certified for installation in a mobile home Installa...

Page 8: ...ed certain distances from adjacent doors operable windows and shrubbery See figure 11 at the end of this chapter CAUTION The unit must be installed level front to back and side to side Adjust front le...

Page 9: ...1738 10 11 7 8 35 14 1744 1739 12 13 7 8 37 16 1745 1740 14 15 7 8 39 18 1769 1770 16 17 7 8 41 20 1771 1772 17 18 7 8 42 21 1773 1774 18 19 7 8 43 22 20 21 7 8 45 24 22 23 7 8 47 26 Table 4 E INSTALL...

Page 10: ...he building drain system Use pvc pipe and fittings field supplied The wall sleeve is equipped with a drain pan that collects rain water entering the wall sleeve and the unit condenser coil area At the...

Page 11: ...ing system during testing Once the gas piping up to the shut off valve has been tested the remaining piping to the unit gas valve must be tested Do not exceed psig or 14 water column for this test or...

Page 12: ...ase the phase wire should be connected to L1 on the contactor An additional wire for unit grounding is required On 208 volt systems the transformer wiring needs to be changed Swap the red transformer...

Page 13: ...TO WINDOW OR DOOR THAT MAY BE OPENED 6 INCHES 15cm FOR APPLIANCES 10 000 Btuh 3kw 12 INCHES 30cm FOR APPLIANCES 10 000 Btuh 3kw AND 100 000 btuh 30kw CANADIAN INSTALLATIONS US INSTALLATIONS 1 2 6 INC...

Page 14: ...back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time of completion of installation the owner shall have a perio...

Page 15: ...to run and the compressor will start Note There will be a 5 minute delay in the compressor starting if the thermostat set point was raised and then lowered again 12 Once the room reaches the set temp...

Page 16: ...r conditioning performance If it is suspected that there is a refrigerant leak in the unit then the charge can be checked by placing a thermometer on the liquid line near the filter dryer and connecti...

Page 17: ...er obstructions Clean the condensate drain and ensure there are no obstructions On DYPA12 models place a thermometer on the compressor suction line above the accumulator Connect a pressure gauge to th...

Page 18: ...14 3 4 32 5 8 28 9 16 32 3 4 DYPA30AC3A 1741 5 7 8 6 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A and DYPA24AC3A 1742 7 7 8 8 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A and DYPA24AC3A 1743 9...

Page 19: ...ted service labor diagnosis calls filter driers refrigerant or any other material charges 2 Damages caused by shipping accident abuse negligence misuse fire flood or Acts of God 3 Damages caused by op...

Page 20: ...existing wires up to Top Line side of contactor 7 Wire as per drawing ES48000 sent with the kit to contactor ground lug 8 Re insert rubber drain hose through bushing with supplied Wires Heat cable 9 I...

Page 21: ...ent un incendie ou une explosion pourrait en r sulter entra nant des dommages mat riels des blessures corporelles ou m me la mort Ne pas entreposer ni utiliser d essence ou d autres vapeurs ou liquide...

Page 22: ...concepteurs et aux constructeurs une alternative conomique pour climatiser plusieurs pi ces dans un complexe d habitation Le DynaPack comporte 1 0 2 5 tonnes de refroidissement 36 60 MBTU de chauffag...

Page 23: ...BK BK 24 V Ca TERRE Y W C R G PK HUM FLAMME 24V INTERRUPTEUR DE FLAMME BL O 230V INDUCTEUR BK R OFM C BK BR WHT ROBINET GAZ INTERRUPTEUR FIN DE COURSE INTERRUPTEUR ROTATIF PRESSOSTAT O BL PK PK R O G...

Page 24: ...ynapack est une unit verticale comprenant un chauffage au gaz avec climatisation lectrique La s curit du Dynapack a t certifi e par Intertek Testing Services conform ment aux codes de s curit nationau...

Page 25: ...d une mani re quelconque autre que celle qui est sp cifi e dans ces instructions L installation doit tre planifi e l avance afin que l emplacement de l vent de l appareil soit conforme aux codes loca...

Page 26: ...e Approx CFM Approx Hausse Temp F Vitesse de refroidissement recommand e Approx CFM DYPA12AC3A036 moyenne 700 38 Bas 400 DYPA12AC3A048 moyenne 700 50 Bas 400 DYPA18AC3A036 moyenne 700 38 moyenne basse...

Page 27: ...t aux codes de s curit nationaux des tats Unis et du Canada Le Dynapack est certifi pour fonctionner au gaz naturel Le Dynapack n est PAS certifi pour installation dans une maison mobile Les installat...

Page 28: ...des buissons Voir la figure 11 la fin de ce chapitre MISE EN GARDE L appareil doit tre install niveau de l avant l arri re et de c t c t Ajustez les pieds de nivellement avant selon besoin B INSTALLAT...

Page 29: ...7 8 31 10 1742 1737 8 9 7 8 33 12 1743 1738 10 11 7 8 35 14 1744 1739 12 13 7 8 37 16 1745 1740 14 15 7 8 39 18 1769 1770 16 17 7 8 41 20 1771 1772 17 18 7 8 42 21 1773 1774 18 19 7 8 43 22 20 21 7 8...

Page 30: ...syst me de drainage du b timent Utilisez des tuyaux de et des raccords en PVC fournis par l installateur Le caisson mural est quip d un bac de r cup ration des eaux de pluie qui p n trent dans le cai...

Page 31: ...ssion d essai de la tuyauterie de gaz Sinon de la vanne de fermeture doit tre retir e du syst me de tuyauterie pendant les tests Une fois que la tuyauterie de gaz a t test e jusqu la vanne de fermetur...

Page 32: ...e est de 208 230 volts phase neutre Dans ce cas le fil de phase doit tre connect L1 sur le contacteur Un fil suppl mentaire pour la mise la terre de l appareil est requis Sur les syst mes 208 volts le...

Page 33: ...LES APPAREILS 50 000 Btuh 15 kW 6 POUCES 15cm POUR LES APPAREILS 10 000 Btuh 3 kW 9 POUCES 23 cm POUR LES APPAREILS 10 000 Btuh 3 kW ET 50 000 Btuh 15 kW 12 POUCES 30 cm POUR LES APPAREILS 50 000 Btuh...

Page 34: ...u prochain tage adjacent b Si les exigences de la pr sente sous section ne peuvent tre satisfaites au moment de l installation le propri taire dispose d un d lai de trente 30 jours pour se conformer a...

Page 35: ...le compresseur se met en marche Remarque il y aura un d lai de 5 minutes au d marrage du compresseur si le point de consigne du thermostat a t lev puis nouveau abaiss 12 Une fois que la pi ce a attei...

Page 36: ...ME L unit a t test e en usine pour assurer des performances appropri es de la climatisation Si l on soup onne une fuite de r frig rant dans l appareil la charge peut tre v rifi e en pla ant un thermom...

Page 37: ...at et assurez vous qu il n y a pas d obstruction Sur les mod les DYPA12 placez un thermom tre sur la conduite d aspiration du compresseur au dessus de l accumulateur Connectez un manom tre au port de...

Page 38: ...14 3 4 32 5 8 28 9 16 32 3 4 DYPA30AC3A 1741 5 7 8 6 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A et DYPA24AC3A 1742 7 7 8 8 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A et DYPA24AC3A 1743 9 7 8...

Page 39: ...ande l ex cution au titre de cette Garantie doit fournir un acc s raisonnable au produit ou la pi ce pr tendument d fectueux ou d faillant Airxcel Commercial Group et ses agents et employ s autoris s...

Page 40: ...t sup rieur ligne du contacteur 7 C blez selon le plan ES48000 envoy avec le kit au contacteur et la cosse de terre 8 R ins rez le tuyau de drainage en caoutchouc dans la bague avec les fils c ble de...

Reviews: