Suburban DynaPack S & H Series Owner's Manual 06/2020 Rev.2
H: GAS SUPPLY
WARNING
Any conversion of an S-Series natural gas unit to liquefied petroleum (LP) gas must be done by qualified personnel
using a conversion kit available from the manufacturer, following the instructions in the conversion kit, If done
improperly, over firing of the burners and improper burner operation can result. This can create carbon monoxide
which could cause asphyxiation.
Only S-Series units may be converted to LP gas.
Minimum gas supply pressure for purposes of input adjustment:
Minimum
Maximum
Natural Gas
5" W.C. *
10" W.C.
Liquefied Petroleum (LP) Gas
11" W.C.
13" W.C.
*Water Column
Table 3
2.3 INSTALLATION, "H" SERIES UNITS
WARNING
Installation of this appliance must be made in accordance with the written instructions provided in this manual.
No agent, representative or employee of Suburban or other person has the authority to change, modify or
waive any provision of the instructions contained in this manual.
WARNING - CARBON-MONOXIDE POISONING HAZARD
Failure to follow instructions could result in severe personal injury or death due to carbon-monoxide poisoning,
if combustion products infiltrate into the building.
Check that all openings in the outside wall around the vent (and air intake) pipe(s) are sealed to prevent
infiltration of combustion products into the building.
Check that furnace vent (and air intake) terminal(s) are not obstructed in any way during all seasons.
The Dynapack units are vertical package units featuring gas fired heating with electrical air conditioning. The Dynapack unit has been
safety certified by Intertek Testing Services to comply with the national safety codes of the USA and Canada. The Dynapack unit is
certified to operate on natural gas.
The Dynapack unit is NOT certified for installation in a mobile home.
Installations in the USA must be in accordance with city, county, or state codes and regulations. If local codes do not apply then the
installation must be made in accordance with the National Fuel Gas Code and the National Electrical Code.
This product is a general purpose heating and cooling product to be installed in a conditioned closet. For hotel guestroom applications,
sound treatment on the closet walls and doors is required to meet the recommended ASHRAE sound criterion and a ducted supply and
return are recommended for best sound performance.
Installations made in Canada likewise must be in accordance with city, provincial, or national codes or the current version of CANI-B149
Installation Code.
WARNING
In the state of Massachusetts: This product must be installed by a licensed Plumber or Gas Fitter. When
flexible connectors are used, the maximum length shall not exceed 36". When lever-type gas shutoffs are
used, they shall be T-handle type.
The outdoor fan discharge or the condenser air intake cannot be connected to field fabricated ducting. This unit can only be installed
using the factory supplied wall sleeves.
A: LOCATION
IMPORTANT
The Dynapack condensate drain system is designed to be installed in a conditioned space. To prevent freezing
of the drain condensate in the P-Trap, the installation location should not be exposed to freezing conditions.
In installations where the drain system is exposed to freezing conditions, we offer an optional heated P-Trap
which is available for purchase. The part number for the heated P-Trap installation kit is K/10348 and the steps
for installation are outlined in Appendix A.