Airxcel Suburban DynaPack H Series Owner'S Manual Download Page 15

 15 

 

Suburban DynaPack S & H Series Owner's Manual 06/2020 Rev.2

Chapter 3: Unit Startup & Operation

 

WARNING

Failure to follow these instructions may lead to a fire, explosion, property damage, personal injury, or loss of 

life. 

 

CAUTION

This furnace is equipped with a direct ignition control Do not attempt to manually light the burners.

BEFORE OPERATING

, smell all around the appliance area for gas. Be sure to smell next to the floor because gas is heavier than air and 

will settle on the floor. If you smell gas STOP. Open the windows and doors to clear out any gas. Recheck all gas piping and connections 

for leaks.

  3.1  TO CHECK UNIT OPERATION 

1.  Make sure the gas valve is switched ON. Remove the gas compartment door. Turn the gas valve knob or move the switch to the 

ON position. See figure 10. Do not use any tools to turn the knob. If you are unable to push in and turn the knob by hand then call 

a qualified service technician for assistance. Replace the gas compartment door.

2.  Turn on electrical power to the unit.
3.  Switch the room thermostat to heat.
4.  Raise the set point to above the room temperature.
5.  The thermostat will call for heat and the combustion blower will begin to operate.
6.  The combustion blower will operate for 15 to 20 seconds before the ignition controls begins sparking, then the gas valve will open 

and the burners will light. The burners can be viewed through the sight glass in the door panel.

7.  The room air blower starts 30 seconds after the burners light.
8.  Once the room reaches the set temperature, the burners turn off and the room air blower turns off 90 seconds later.
9.  Switch the room thermostat over to cooling.
10. Lower the set point to below the room temperature.
11. After a slight delay the room air blower will begin to run and the compressor will start. Note: There will be a 5 minute delay in the 

compressor starting if the thermostat set point was raised and then lowered again.

12. Once the room reaches the set temperature, the compressor will turn off and the room air blower will turn off 30 seconds later.

  3.2  TO SHUT DOWN UNIT 

To turn off the unit switch the room thermostat to OFF. Turn the electrical power off and close the manual gas supply valve before 

performing any service to the unit.

  3.3  HEATING ADJUSTMENTS 

1.  Turn off the unit at the room thermostat and shut off the manual gas valve. 
2.  Connect a pressure gauge with suitable range (0 to 10” for natural and 0 to 15” for LP) to the inlet pressure port on the gas valve. 

See figure 10.

3.  Open the manual gas valve and turn the unit on.
4.  Once the furnace is operating, check the inlet gas pressure. Adjust the pressure regulator to obtain an inlet pressure of 5” to 10” 

water column for natural gas and 11” to 13” for LP gas.

5.  Turn off the unit and shut off the manual gas valve.
6.  Move the pressure gauge to the manifold pressure port on the gas valve. See figure 10.
7.  Once the furnace is operating, check the manifold pressure. Adjust the gas valve pressure regulator to obtain a manifold pressure 

of 3.5” water column for natural gas and 10.0” water column for LP gas. 

8.  On natural gas installations the input to the furnace must be checked to insure safe operation. Any other gas appliances that use 

the gas meter must be turned off including the pilot lights. 

9.  With the Dynapack furnace running, count the time it takes for the gas meter to make one revolution. Also record the gas meter 

rate of cubic feet per revolution. You will also need the average heating value of the natural gas for your location. Plug these factors 

into the equation below to calculate the gas input rate to the furnace in BTU per hour.

BTU/HR Input

=

Cubic Feet Per Revolution

X 3600 X Heating 

Valve

Number of Seconds Per Revolution

Summary of Contents for Suburban DynaPack H Series

Page 1: ...m WARNING If the information in these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other...

Page 2: ...and cooling system that provides designers and builders with a cost effective alternative to condition multiple rooms in a multi unit housing application The DynaPack features 1 to 2 5 Tons Cooling 36...

Page 3: ...R CC BK BK BK 24 VAC GROUND Y W C R G PK HUM FLAME 24V FLAME SWITCH BL O 230V INDUCER BK R OFM C BK BR WHT GAS VALVE SWITCH HIGH LIMIT ROLLOUT SWITCH SWITCH PRESSURE O BL PK PK R O G BL Y BL BL BL O N...

Page 4: ...units are vertical package units featuring gas fired heating with electrical air conditioning The Dynapack unit has been safety certified by Intertek Testing Services to comply with the national safet...

Page 5: ...in any manner other than what is specified in these instructions The installation must be planned before hand so that the unit exhaust vent location complies with local or national codes in regards t...

Page 6: ...of the units on each of the indoor blower speeds Table 4 lists the recommended heating and cooling speeds with its approximate cfm delivery Use both tables to properly design the duct system for both...

Page 7: ...es to comply with the national safety codes of the USA and Canada The Dynapack unit is certified to operate on natural gas The Dynapack unit is NOT certified for installation in a mobile home Installa...

Page 8: ...ed certain distances from adjacent doors operable windows and shrubbery See figure 11 at the end of this chapter CAUTION The unit must be installed level front to back and side to side Adjust front le...

Page 9: ...1738 10 11 7 8 35 14 1744 1739 12 13 7 8 37 16 1745 1740 14 15 7 8 39 18 1769 1770 16 17 7 8 41 20 1771 1772 17 18 7 8 42 21 1773 1774 18 19 7 8 43 22 20 21 7 8 45 24 22 23 7 8 47 26 Table 4 E INSTALL...

Page 10: ...he building drain system Use pvc pipe and fittings field supplied The wall sleeve is equipped with a drain pan that collects rain water entering the wall sleeve and the unit condenser coil area At the...

Page 11: ...ing system during testing Once the gas piping up to the shut off valve has been tested the remaining piping to the unit gas valve must be tested Do not exceed psig or 14 water column for this test or...

Page 12: ...ase the phase wire should be connected to L1 on the contactor An additional wire for unit grounding is required On 208 volt systems the transformer wiring needs to be changed Swap the red transformer...

Page 13: ...TO WINDOW OR DOOR THAT MAY BE OPENED 6 INCHES 15cm FOR APPLIANCES 10 000 Btuh 3kw 12 INCHES 30cm FOR APPLIANCES 10 000 Btuh 3kw AND 100 000 btuh 30kw CANADIAN INSTALLATIONS US INSTALLATIONS 1 2 6 INC...

Page 14: ...back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time of completion of installation the owner shall have a perio...

Page 15: ...to run and the compressor will start Note There will be a 5 minute delay in the compressor starting if the thermostat set point was raised and then lowered again 12 Once the room reaches the set temp...

Page 16: ...r conditioning performance If it is suspected that there is a refrigerant leak in the unit then the charge can be checked by placing a thermometer on the liquid line near the filter dryer and connecti...

Page 17: ...er obstructions Clean the condensate drain and ensure there are no obstructions On DYPA12 models place a thermometer on the compressor suction line above the accumulator Connect a pressure gauge to th...

Page 18: ...14 3 4 32 5 8 28 9 16 32 3 4 DYPA30AC3A 1741 5 7 8 6 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A and DYPA24AC3A 1742 7 7 8 8 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A and DYPA24AC3A 1743 9...

Page 19: ...ted service labor diagnosis calls filter driers refrigerant or any other material charges 2 Damages caused by shipping accident abuse negligence misuse fire flood or Acts of God 3 Damages caused by op...

Page 20: ...existing wires up to Top Line side of contactor 7 Wire as per drawing ES48000 sent with the kit to contactor ground lug 8 Re insert rubber drain hose through bushing with supplied Wires Heat cable 9 I...

Page 21: ...ent un incendie ou une explosion pourrait en r sulter entra nant des dommages mat riels des blessures corporelles ou m me la mort Ne pas entreposer ni utiliser d essence ou d autres vapeurs ou liquide...

Page 22: ...concepteurs et aux constructeurs une alternative conomique pour climatiser plusieurs pi ces dans un complexe d habitation Le DynaPack comporte 1 0 2 5 tonnes de refroidissement 36 60 MBTU de chauffag...

Page 23: ...BK BK 24 V Ca TERRE Y W C R G PK HUM FLAMME 24V INTERRUPTEUR DE FLAMME BL O 230V INDUCTEUR BK R OFM C BK BR WHT ROBINET GAZ INTERRUPTEUR FIN DE COURSE INTERRUPTEUR ROTATIF PRESSOSTAT O BL PK PK R O G...

Page 24: ...ynapack est une unit verticale comprenant un chauffage au gaz avec climatisation lectrique La s curit du Dynapack a t certifi e par Intertek Testing Services conform ment aux codes de s curit nationau...

Page 25: ...d une mani re quelconque autre que celle qui est sp cifi e dans ces instructions L installation doit tre planifi e l avance afin que l emplacement de l vent de l appareil soit conforme aux codes loca...

Page 26: ...e Approx CFM Approx Hausse Temp F Vitesse de refroidissement recommand e Approx CFM DYPA12AC3A036 moyenne 700 38 Bas 400 DYPA12AC3A048 moyenne 700 50 Bas 400 DYPA18AC3A036 moyenne 700 38 moyenne basse...

Page 27: ...t aux codes de s curit nationaux des tats Unis et du Canada Le Dynapack est certifi pour fonctionner au gaz naturel Le Dynapack n est PAS certifi pour installation dans une maison mobile Les installat...

Page 28: ...des buissons Voir la figure 11 la fin de ce chapitre MISE EN GARDE L appareil doit tre install niveau de l avant l arri re et de c t c t Ajustez les pieds de nivellement avant selon besoin B INSTALLAT...

Page 29: ...7 8 31 10 1742 1737 8 9 7 8 33 12 1743 1738 10 11 7 8 35 14 1744 1739 12 13 7 8 37 16 1745 1740 14 15 7 8 39 18 1769 1770 16 17 7 8 41 20 1771 1772 17 18 7 8 42 21 1773 1774 18 19 7 8 43 22 20 21 7 8...

Page 30: ...syst me de drainage du b timent Utilisez des tuyaux de et des raccords en PVC fournis par l installateur Le caisson mural est quip d un bac de r cup ration des eaux de pluie qui p n trent dans le cai...

Page 31: ...ssion d essai de la tuyauterie de gaz Sinon de la vanne de fermeture doit tre retir e du syst me de tuyauterie pendant les tests Une fois que la tuyauterie de gaz a t test e jusqu la vanne de fermetur...

Page 32: ...e est de 208 230 volts phase neutre Dans ce cas le fil de phase doit tre connect L1 sur le contacteur Un fil suppl mentaire pour la mise la terre de l appareil est requis Sur les syst mes 208 volts le...

Page 33: ...LES APPAREILS 50 000 Btuh 15 kW 6 POUCES 15cm POUR LES APPAREILS 10 000 Btuh 3 kW 9 POUCES 23 cm POUR LES APPAREILS 10 000 Btuh 3 kW ET 50 000 Btuh 15 kW 12 POUCES 30 cm POUR LES APPAREILS 50 000 Btuh...

Page 34: ...u prochain tage adjacent b Si les exigences de la pr sente sous section ne peuvent tre satisfaites au moment de l installation le propri taire dispose d un d lai de trente 30 jours pour se conformer a...

Page 35: ...le compresseur se met en marche Remarque il y aura un d lai de 5 minutes au d marrage du compresseur si le point de consigne du thermostat a t lev puis nouveau abaiss 12 Une fois que la pi ce a attei...

Page 36: ...ME L unit a t test e en usine pour assurer des performances appropri es de la climatisation Si l on soup onne une fuite de r frig rant dans l appareil la charge peut tre v rifi e en pla ant un thermom...

Page 37: ...at et assurez vous qu il n y a pas d obstruction Sur les mod les DYPA12 placez un thermom tre sur la conduite d aspiration du compresseur au dessus de l accumulateur Connectez un manom tre au port de...

Page 38: ...14 3 4 32 5 8 28 9 16 32 3 4 DYPA30AC3A 1741 5 7 8 6 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A et DYPA24AC3A 1742 7 7 8 8 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A et DYPA24AC3A 1743 9 7 8...

Page 39: ...ande l ex cution au titre de cette Garantie doit fournir un acc s raisonnable au produit ou la pi ce pr tendument d fectueux ou d faillant Airxcel Commercial Group et ses agents et employ s autoris s...

Page 40: ...t sup rieur ligne du contacteur 7 C blez selon le plan ES48000 envoy avec le kit au contacteur et la cosse de terre 8 R ins rez le tuyau de drainage en caoutchouc dans la bague avec les fils c ble de...

Reviews: