CFM INTÉRIEUR vs PRESSION STATIQUE (serpentin sec + pas de filtre à air)

Numéro de modèle

Vitesse 

de la 

soufflante

0,10" ce

0,15" ce

0,20" ce

0,25" ce

0,30" ce

0,40" ce

0,50" ce

0,60" ce

0,70" ce

0,80" ce

DYPA12AC3A***

BAS

497

473

448

424

400

348

296

247

212

160

MOY BAS

577

562

547

522

497

458

415

357

317

281

MED

757

748

739

716

692

670

635

586

558

521

MOY HAUT

937

920

905

888

872

852

827

790

728

677

HI

1060

1050

1042

1015

977

927

876

824

758

700

DYPA18AC3A***

BAS

512

491

469

428

387

320

285

250

213

179

MOY BAS

596

568

540

522

504

447

415

381

324

291

MED

773

761

748

730

711

675

640

622

586

550

MOY HAUT

972

955

938

927

915

874

850

825

796

766

HAUT

1108

1091

1074

1057

1039

1002

970

917

868

796

DYPA24AC3A***

BAS

504

483

461

420

379

312

252

207

N/R

N/R

MOY BAS

588

560

532

514

496

439

377

320

262

202

MED

765

753

740

722

703

667

622

572

532

482

MOY HAUT

964

947

930

919

907

866

828

782

757

702

HI

1100

1083

1066

1049

1031

994

962

922

882

827

DYPA30AC3A***

BAS

490

465

440

415

385

310

225

170

N/R

N/R

MOY BAS

570

540

520

500

476

415

365

310

250

205

MED

768

755

741

732

704

666

621

580

535

500

MOY HAUT

934

922

913

895

873

835

800

760

730

690

HI

1064

1046

1017

1009

995

965

935

900

875

828

Tableau 9

TERMINAL DE L'ÉVENT

ALIMENTATION D’AIR

X

ZONE OÙ LE TERMINAL N'EST PAS AUTORISÉ

A=

DÉGAGEMENT AU-DESSUS DU 

NIVEAU DU SOL, VÉRANDA, 

PORCHE, TERRACE OU BALCON

12 POUCES (30 cm) 

(VOIR NOTE a)

12 POUCES (30 cm) 

(VOIR NOTE a)

J=

DÉGAGEMENT À L'ADMISSION 

D'AIR NON MÉCANIQUE AU 

BÂTIMENT, OU ENTRE 

L'ADMISSION D'AIR DE 

COMBUSTION ET TOUT 

AUTRE APPAREIL.

6 POUCES (15 cm) POUR LES APPAREILS 

< 10 000 Btuh (3 kW), 12 POUCES (30 cm) 

POUR LES APPAREILS > 10 000 Btuh (3 kW)

ET < 100 000 Btuh (30 kW) 

6 POUCES (15 cm) POUR LES APPAREILS 

< 10 000 Btuh (3 kW), 12 POUCES (30 cm) 

POUR LES APPAREILS > 10 000 Btuh (3 kW)

ET < 100 000 Btuh (30 kW) 

6 POUCES (15cm) POUR LES APPAREILS

< 10 000 Btuh (3 kW),

9 POUCES (23 cm) POUR LES APPAREILS

> 10 000 Btuh (3 kW) ET < 50 000

Btuh (15 kW)

12 POUCES (30 cm) POUR LES APPAREILS

> 50 000 Btuh (15 kW)

6 POUCES (15cm) POUR LES APPAREILS

< 10 000 Btuh (3 kW),

9 POUCES (23 cm) POUR LES APPAREILS

> 10 000 Btuh (3 kW) ET < 50 000

Btuh (15 kW)

12 POUCES (30 cm) POUR LES APPAREILS

> 50 000 Btuh (15 kW)

 

B=

DÉGAGEMENT À FENÊTRE OU 

PORTE POUVANT ÊTRE OUVERTE

INSTALLATIONS AU CANADA

INSTALLATIONS AUX ÉTATS-UNIS

1

2

K=

DÉGAGEMENT À UNE 

ADMISSION D'AIR MÉCANIQUE

6 PIEDS (1,83m)

3 PIEDS (91 cm) AU-DESSUS SI À MOINS 

DE 10 PIEDS (3 m) HORIZONTALEMENT 

C=

DÉGAGEMENT À FENÊTRE OU 

PORTE POUVANT ÊTRE OUVERTE

* a

* a

L=

DÉGAGEMENT AU-DESSUS D'UN 

TROTTOIR PAVÉ OU D'UNE ALLÉE 

PAVÉE SITUÉS SUR UNE 

PROPRIÉTÉ PUBLIQUE 

7 PIEDS (2,13m)

* a

D=

DÉGAGEMENT VERTICAL AU 

SOFFITE VENTILÉ SITUÉ 

AU-DESSUS DU TERMINAL À UNE 

DISTANCE HORIZONTALE DE 

2 PIEDS (61 cm) DE L'AXE DU 

TERMINAL

* a

* a

M=

DÉGAGEMENT SOUS VÉRANDA, 

PORCHE, TERRACE OU BALCON

12 POUCES (30 cm) 

* a

E=

DÉGAGEMENT AU SOFFITE NON VENTILÉ

* a

* a

F=

DÉGAGEMENT AU COIN EXTÉRIEUR

* a

* a

G=

DÉGAGEMENT AU COIN INTÉRIEUR

* a

* a

H=

DÉGAGEMENT DE CHAQUE CÔTÉ 

DE LA LIGNE CENTRALE ÉTENDUE

 AU-DESSUS DU COMPTEUR 

OU RÉGULATEUR

3 PIEDS (91 cm) DANS UNE HAUTEUR DE 15 PIEDS 

(4,5 m) AU-DESSUS DU COMPTEUR OU RÉGULATEUR

* a

I=

DÉGAGEMENT POUR LE SERVICE 

DE LA SORTIE DE L'ÉVENT DU 

RÉGULATEUR 

3 PIEDS (91 cm)

* a

1

CONFORMÉMENT AU CODE ACTUEL CSA B149.1, CODE D'INSTALLATION DE GAZ NATUREL ET DE PROPANE 

2

CONFORMÉMENT À ANSI Z223.1 / NFPA 54 ACTUEL, CODE NATIONAL DE GAZ COMBUSTIBLE

UN ÉVENT NE DOIT PAS SE TERMINER DIRECTEMENT AU-DESSUS D'UN TROTTOIR OU D'UNE ALLÉE PAVÉE QUI SE TROUVE ENTRE 

DEUX HABITATIONS UNIFAMILIALES ET QUI SERT AUX DEUX LOGEMENTS

PERMIS SEULEMENT SI LA VÉRANDA, LE PORCHE, LA TERRACE OU LE BALCON SONT ENTIÈREMENT OUVERTS SUR AU MINUMUM 

DEUX CÔTÉS SOUS LE PLANCHER.
POUR LES DÉGAGEMENTS NON SPÉCIFIÉS DANS LES NORMES ANSI Z223.1/NFPA 54 OU CSA B149.1, L'UN DES ÉLÉMENTS 

SUIVANTS DOIT ÊTRE INDIQUÉ :

*

UNE RÉFÉRENCE À LA NOTE DE BAS DE PAGE SUIVANTE :

"DÉGAGEMENT CONFORMÉMENT AUX CODES D'INSTALLATION LOCAUX, AUX EXIGENCES DU FOURNISSEUR DE GAZ ET AUX 

INSTRUCTIONS D'INSTALLATION DU FABRICANT (VOIR LE MANUEL FOURNI AVEC L'APPAREIL)

a)

OUVRANTE

FIXE 

FERMÉE

FIXE 

FERMÉE

DÉTAIL

 DE 

COIN INTÉRIEUR

G

OUVRANTE

A

C

F

B

B

B

B

A

J

B

I

H

M

K

E

D

L

B

INSTALLATIONS AU CANADA

INSTALLATIONS AUX ÉTATS-UNIS

1

2

Figure 11

Summary of Contents for Suburban DynaPack H Series

Page 1: ...m WARNING If the information in these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other...

Page 2: ...and cooling system that provides designers and builders with a cost effective alternative to condition multiple rooms in a multi unit housing application The DynaPack features 1 to 2 5 Tons Cooling 36...

Page 3: ...R CC BK BK BK 24 VAC GROUND Y W C R G PK HUM FLAME 24V FLAME SWITCH BL O 230V INDUCER BK R OFM C BK BR WHT GAS VALVE SWITCH HIGH LIMIT ROLLOUT SWITCH SWITCH PRESSURE O BL PK PK R O G BL Y BL BL BL O N...

Page 4: ...units are vertical package units featuring gas fired heating with electrical air conditioning The Dynapack unit has been safety certified by Intertek Testing Services to comply with the national safet...

Page 5: ...in any manner other than what is specified in these instructions The installation must be planned before hand so that the unit exhaust vent location complies with local or national codes in regards t...

Page 6: ...of the units on each of the indoor blower speeds Table 4 lists the recommended heating and cooling speeds with its approximate cfm delivery Use both tables to properly design the duct system for both...

Page 7: ...es to comply with the national safety codes of the USA and Canada The Dynapack unit is certified to operate on natural gas The Dynapack unit is NOT certified for installation in a mobile home Installa...

Page 8: ...ed certain distances from adjacent doors operable windows and shrubbery See figure 11 at the end of this chapter CAUTION The unit must be installed level front to back and side to side Adjust front le...

Page 9: ...1738 10 11 7 8 35 14 1744 1739 12 13 7 8 37 16 1745 1740 14 15 7 8 39 18 1769 1770 16 17 7 8 41 20 1771 1772 17 18 7 8 42 21 1773 1774 18 19 7 8 43 22 20 21 7 8 45 24 22 23 7 8 47 26 Table 4 E INSTALL...

Page 10: ...he building drain system Use pvc pipe and fittings field supplied The wall sleeve is equipped with a drain pan that collects rain water entering the wall sleeve and the unit condenser coil area At the...

Page 11: ...ing system during testing Once the gas piping up to the shut off valve has been tested the remaining piping to the unit gas valve must be tested Do not exceed psig or 14 water column for this test or...

Page 12: ...ase the phase wire should be connected to L1 on the contactor An additional wire for unit grounding is required On 208 volt systems the transformer wiring needs to be changed Swap the red transformer...

Page 13: ...TO WINDOW OR DOOR THAT MAY BE OPENED 6 INCHES 15cm FOR APPLIANCES 10 000 Btuh 3kw 12 INCHES 30cm FOR APPLIANCES 10 000 Btuh 3kw AND 100 000 btuh 30kw CANADIAN INSTALLATIONS US INSTALLATIONS 1 2 6 INC...

Page 14: ...back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time of completion of installation the owner shall have a perio...

Page 15: ...to run and the compressor will start Note There will be a 5 minute delay in the compressor starting if the thermostat set point was raised and then lowered again 12 Once the room reaches the set temp...

Page 16: ...r conditioning performance If it is suspected that there is a refrigerant leak in the unit then the charge can be checked by placing a thermometer on the liquid line near the filter dryer and connecti...

Page 17: ...er obstructions Clean the condensate drain and ensure there are no obstructions On DYPA12 models place a thermometer on the compressor suction line above the accumulator Connect a pressure gauge to th...

Page 18: ...14 3 4 32 5 8 28 9 16 32 3 4 DYPA30AC3A 1741 5 7 8 6 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A and DYPA24AC3A 1742 7 7 8 8 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A and DYPA24AC3A 1743 9...

Page 19: ...ted service labor diagnosis calls filter driers refrigerant or any other material charges 2 Damages caused by shipping accident abuse negligence misuse fire flood or Acts of God 3 Damages caused by op...

Page 20: ...existing wires up to Top Line side of contactor 7 Wire as per drawing ES48000 sent with the kit to contactor ground lug 8 Re insert rubber drain hose through bushing with supplied Wires Heat cable 9 I...

Page 21: ...ent un incendie ou une explosion pourrait en r sulter entra nant des dommages mat riels des blessures corporelles ou m me la mort Ne pas entreposer ni utiliser d essence ou d autres vapeurs ou liquide...

Page 22: ...concepteurs et aux constructeurs une alternative conomique pour climatiser plusieurs pi ces dans un complexe d habitation Le DynaPack comporte 1 0 2 5 tonnes de refroidissement 36 60 MBTU de chauffag...

Page 23: ...BK BK 24 V Ca TERRE Y W C R G PK HUM FLAMME 24V INTERRUPTEUR DE FLAMME BL O 230V INDUCTEUR BK R OFM C BK BR WHT ROBINET GAZ INTERRUPTEUR FIN DE COURSE INTERRUPTEUR ROTATIF PRESSOSTAT O BL PK PK R O G...

Page 24: ...ynapack est une unit verticale comprenant un chauffage au gaz avec climatisation lectrique La s curit du Dynapack a t certifi e par Intertek Testing Services conform ment aux codes de s curit nationau...

Page 25: ...d une mani re quelconque autre que celle qui est sp cifi e dans ces instructions L installation doit tre planifi e l avance afin que l emplacement de l vent de l appareil soit conforme aux codes loca...

Page 26: ...e Approx CFM Approx Hausse Temp F Vitesse de refroidissement recommand e Approx CFM DYPA12AC3A036 moyenne 700 38 Bas 400 DYPA12AC3A048 moyenne 700 50 Bas 400 DYPA18AC3A036 moyenne 700 38 moyenne basse...

Page 27: ...t aux codes de s curit nationaux des tats Unis et du Canada Le Dynapack est certifi pour fonctionner au gaz naturel Le Dynapack n est PAS certifi pour installation dans une maison mobile Les installat...

Page 28: ...des buissons Voir la figure 11 la fin de ce chapitre MISE EN GARDE L appareil doit tre install niveau de l avant l arri re et de c t c t Ajustez les pieds de nivellement avant selon besoin B INSTALLAT...

Page 29: ...7 8 31 10 1742 1737 8 9 7 8 33 12 1743 1738 10 11 7 8 35 14 1744 1739 12 13 7 8 37 16 1745 1740 14 15 7 8 39 18 1769 1770 16 17 7 8 41 20 1771 1772 17 18 7 8 42 21 1773 1774 18 19 7 8 43 22 20 21 7 8...

Page 30: ...syst me de drainage du b timent Utilisez des tuyaux de et des raccords en PVC fournis par l installateur Le caisson mural est quip d un bac de r cup ration des eaux de pluie qui p n trent dans le cai...

Page 31: ...ssion d essai de la tuyauterie de gaz Sinon de la vanne de fermeture doit tre retir e du syst me de tuyauterie pendant les tests Une fois que la tuyauterie de gaz a t test e jusqu la vanne de fermetur...

Page 32: ...e est de 208 230 volts phase neutre Dans ce cas le fil de phase doit tre connect L1 sur le contacteur Un fil suppl mentaire pour la mise la terre de l appareil est requis Sur les syst mes 208 volts le...

Page 33: ...LES APPAREILS 50 000 Btuh 15 kW 6 POUCES 15cm POUR LES APPAREILS 10 000 Btuh 3 kW 9 POUCES 23 cm POUR LES APPAREILS 10 000 Btuh 3 kW ET 50 000 Btuh 15 kW 12 POUCES 30 cm POUR LES APPAREILS 50 000 Btuh...

Page 34: ...u prochain tage adjacent b Si les exigences de la pr sente sous section ne peuvent tre satisfaites au moment de l installation le propri taire dispose d un d lai de trente 30 jours pour se conformer a...

Page 35: ...le compresseur se met en marche Remarque il y aura un d lai de 5 minutes au d marrage du compresseur si le point de consigne du thermostat a t lev puis nouveau abaiss 12 Une fois que la pi ce a attei...

Page 36: ...ME L unit a t test e en usine pour assurer des performances appropri es de la climatisation Si l on soup onne une fuite de r frig rant dans l appareil la charge peut tre v rifi e en pla ant un thermom...

Page 37: ...at et assurez vous qu il n y a pas d obstruction Sur les mod les DYPA12 placez un thermom tre sur la conduite d aspiration du compresseur au dessus de l accumulateur Connectez un manom tre au port de...

Page 38: ...14 3 4 32 5 8 28 9 16 32 3 4 DYPA30AC3A 1741 5 7 8 6 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A et DYPA24AC3A 1742 7 7 8 8 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A et DYPA24AC3A 1743 9 7 8...

Page 39: ...ande l ex cution au titre de cette Garantie doit fournir un acc s raisonnable au produit ou la pi ce pr tendument d fectueux ou d faillant Airxcel Commercial Group et ses agents et employ s autoris s...

Page 40: ...t sup rieur ligne du contacteur 7 C blez selon le plan ES48000 envoy avec le kit au contacteur et la cosse de terre 8 R ins rez le tuyau de drainage en caoutchouc dans la bague avec les fils c ble de...

Reviews: