CONTROL SYSTEM
Service Manual-CN Fixed RPM series
12-12
(b)
In
RC and SH groups
, whenever
COMP & HE are both OFF
, excluding
protection modes, IFAN operation will be according to the following:
In
other models
IFAN will operate in low speed for 30 sec and then stop. If
COMP is OFF for more than 3 minutes and IFEEL Mode is inactive, IFAN will
operate in low speed according to the following graph:
IFAN (Low Speed)
(c) In
RH group
, IFAN starts when HE starts. When HE switches to OFF, IFAN
switches to LOW for 30 sec and then stops.
4. HE
operation
(a) For
all Groups
, HE can be ON only when IFAN is ON.
(b) For
all Groups
, HE switches to OFF when ICT > 50
o
c, and is activated again
when ICT
d
45
o
c.
(c) In
SH or RC group
, HE operation is limited by the following graph:
HE
ON
OFF
30
45
50
ICT [
o
c]
15
General :
For WAX :
35
20
40
(d) Back-up mode for
SH group
After COMP has been working for 5 minutes, HE & IFAN are activated even if the
ICT is still below 35
o
c. This situation is called Back-up Mode. Both HE & IFAN will
work in Back-up Mode until the ICT reaches 35
o
c. Then, the operation goes on in
the usual mode
Summary of Contents for ONG3-17 R410A
Page 1: ...CN Fixed RPM Series REFRIGERANT R410A HEATPUMP REV 01 Oct 2008...
Page 21: ...Pressure Curves Service Manual CN Fixed RPM series 6 2 6 1 2 Heating...
Page 23: ...Pressure Curves Service Manual CN Fixed RPM series 6 4 6 2 2 Heating...
Page 25: ...Pressure Curves Service Manual CN Fixed RPM series 6 6 6 3 2 Heating...
Page 27: ...Sound Level Characteristices Service Manual CN Fixed RPM series 7 2...
Page 29: ...Sound Level Characteristices Service Manual CN Fixed RPM series 7 4...
Page 86: ...EXPLODED VIEWS AND SPARE PARTS LISTS Service Manual CN Fixed RPM series 14 2 17...
Page 119: ...PROTECTION 468100326...
Page 121: ......
Page 122: ...3...
Page 124: ......
Page 125: ......
Page 127: ......