CONTROL SYSTEM
Service Manual-CN Fixed RPM series
12-7
Cases for disabling thermistor short/disconnected detection
1. The detection of thermistor faults (a) and (b) above, are disabled when Deicer
Protection is started. The detection will be enabled again only after (1) the deicing
is completed, and (2) COMP has been restarted and operated for 30 sec.
2. When all the following conditions are fulfilled:
a. 4.7K Ohm resistor is connected on the OCT
b. IFAN is OFF
c. Compressor is ON
d. ICT < -30 (disconnected)
This condition come to detect and prevent IFAN operation in Deicer in multi spilt
units.
Handling the thermistor faults in a COMP unit
i.
ICT/OCT thermistor is disconnected or shorted -
The invalid thermistor temperature is replaced by 43
o
c, so that the unit can
continue the normal operation. All protections related to that faulty thermistor
will be disabled. For example, in case of any ICT fault, the ICT high pressure
protection in Heat Mode and ICT defrost protection in Cool Mode will not operate
anymore. The same is also applied to the OCT fault.
There is an EEPROM option that, when the OCT thermistor is not connected, the
buzzer will be ON continuously until the user turn off the alarm by
(i)
switching the unit to STBY using a R/C, or
(ii)
pressing the mode switch once.
Once the alarm is turned OFF, it will not be active again unless the unit is reset.
ii.
RAT thermistor is disconnected or shorted –
The RAT will be derived from the ICT by using the equations :
Heat
Mode:
RAT=ICT/2.3
Cool Mode: RAT=ICT*4
Notes:
1. In case of Shorted/Disconnected thermistor failure, the STBY LED
will be blinking until the fault condition is corrected. In case of “Temp
No change” fault the STBY LED will never blink.
2.
User can use the system diagnostics function to find out the nature of
the thermistor faults.
Notes:
1. As in the COMP unit, the STBY LED will be blinking to indicate a
thermistor fault. And, the user can use the system diagnostics
function to find out the nature of the fault.
Summary of Contents for ONG3-17 R410A
Page 1: ...CN Fixed RPM Series REFRIGERANT R410A HEATPUMP REV 01 Oct 2008...
Page 21: ...Pressure Curves Service Manual CN Fixed RPM series 6 2 6 1 2 Heating...
Page 23: ...Pressure Curves Service Manual CN Fixed RPM series 6 4 6 2 2 Heating...
Page 25: ...Pressure Curves Service Manual CN Fixed RPM series 6 6 6 3 2 Heating...
Page 27: ...Sound Level Characteristices Service Manual CN Fixed RPM series 7 2...
Page 29: ...Sound Level Characteristices Service Manual CN Fixed RPM series 7 4...
Page 86: ...EXPLODED VIEWS AND SPARE PARTS LISTS Service Manual CN Fixed RPM series 14 2 17...
Page 119: ...PROTECTION 468100326...
Page 121: ......
Page 122: ...3...
Page 124: ......
Page 125: ......
Page 127: ......