CONTROL SYSTEM
Service Manual-CN Fixed RPM series
12-23
Note:
1. The ICT is also monitored during Cool and Dry mode, in case the RV control circuit is
faulty. Whenever ICT reaches 70
o
c, which indicates a high pressure in the indoor
coil, the COMP will be forced off automatically. The COMP can be turned on again
only after the ICT is under 70
o
c again and after the 3 min COMP ON delay time.
The OPER LED will not blink in this case.
2. Parameters values:
Parameter Regular
Fix-RPM unit
Water Source Heat
Pump Unit
HPC1
52 38
HPC2
55 42
HPC3
61 45
HPC4
66 48
3. Low Condensing Protection
Mode:
(Auto) Cooling or Dry
Temp:
Selected desired temp.
Fan: Any
Timer: Any
I Feel:
On or Off
Unit: Enabled only in WSHP units type (Disabled for all other unit types).
Control Function
To protect the COMP from Low condensing pressure built-up in the outdoor coil during normal
cooling operation, by switching OFF the COMP.
OCT
Forced OFF
Any (ON/OFF)
8
6
Any
(On/Off/Blink)
Blink
Summary of Contents for ONG3-17 R410A
Page 1: ...CN Fixed RPM Series REFRIGERANT R410A HEATPUMP REV 01 Oct 2008...
Page 21: ...Pressure Curves Service Manual CN Fixed RPM series 6 2 6 1 2 Heating...
Page 23: ...Pressure Curves Service Manual CN Fixed RPM series 6 4 6 2 2 Heating...
Page 25: ...Pressure Curves Service Manual CN Fixed RPM series 6 6 6 3 2 Heating...
Page 27: ...Sound Level Characteristices Service Manual CN Fixed RPM series 7 2...
Page 29: ...Sound Level Characteristices Service Manual CN Fixed RPM series 7 4...
Page 86: ...EXPLODED VIEWS AND SPARE PARTS LISTS Service Manual CN Fixed RPM series 14 2 17...
Page 119: ...PROTECTION 468100326...
Page 121: ......
Page 122: ...3...
Page 124: ......
Page 125: ......
Page 127: ......