CONTROL SYSTEM
Service Manual-CN Fixed RPM series
12-11
12.5 HEATING MODE
12.5.1 Heating Mode – General
1. In heating Mode, temp. compensation schedule will be activated for wall mounted,
ducted models, and ceiling mounted (i.e. NKN, CN, and NFC) according to the following
table:
Add to SPT
SPT [
o
c]
I-FEEL ON
I-FEEL OFF
18
d
SPT
d
27
0
o
c
+2
o
c
27 < SPT
d
30
0
o
c
+3
o
c
Notes :
1) compensation will be activated in Forced operation modes
2. RV is OFF in RH group.
3. IF operating rules
(a)
As a general rule for
RC and SH groups
, when
COMP is ON
, excluding protection
modes, IFAN will be switched ON if
x
ICT > 35
o
c or
x
at the 30 second
(4)
after the COMP is switched ON. In this
case, the IFAN will be started at low speed
(5)
.
IFAN Speed
Any
Low
Stop
30
35
40
ICT [
o
c]
Notes :
.
1) In
SH or RC group
, if HE is set to OFF due to low ICT, IFAN will be switched
to LOW and will be turned OFF after 30 sec.
2) An exception to this rule is the Back-up mode for SH group. 3)
3) If the IFAN is turned ON by the 30 seconds operation, its minimum operation
time before stopping due to low ICT temperature is 60 sec.
Summary of Contents for ONG3-17 R410A
Page 1: ...CN Fixed RPM Series REFRIGERANT R410A HEATPUMP REV 01 Oct 2008...
Page 21: ...Pressure Curves Service Manual CN Fixed RPM series 6 2 6 1 2 Heating...
Page 23: ...Pressure Curves Service Manual CN Fixed RPM series 6 4 6 2 2 Heating...
Page 25: ...Pressure Curves Service Manual CN Fixed RPM series 6 6 6 3 2 Heating...
Page 27: ...Sound Level Characteristices Service Manual CN Fixed RPM series 7 2...
Page 29: ...Sound Level Characteristices Service Manual CN Fixed RPM series 7 4...
Page 86: ...EXPLODED VIEWS AND SPARE PARTS LISTS Service Manual CN Fixed RPM series 14 2 17...
Page 119: ...PROTECTION 468100326...
Page 121: ......
Page 122: ...3...
Page 124: ......
Page 125: ......
Page 127: ......