CONTROL SYSTEM
Service Manual-CN Fixed RPM series
12-5
12.3 GENERAL FUNCTIONS FOR ALL MODELS
12.3.1
COMP
operation
For each Mode including POWER OFF & SB, a Min time delay of 3 min before COMP
restarting, excluding DEICING Mode
The Min operation time of COMP under different operating conditions is
Operation Mode
Min operation time of
COMP
Heat, Cool or Auto Modes
3 min.
Fan, Dry, Overflow, Protection modes, or mode change
ignored
12.3.2
IFAN
operation
Min time interval between IFAN speed change in AUTOFAN Mode, is 30 sec.
Min time interval between IFAN speed change in H/M/L Mode is 1 sec.
IFAN speed in Heat/Cool Autofan Mode is determined according to the following table:
'
T
IFAN Speed
'
T
t
2
HIGH
2
t '
T
t
1
MED
1
t '
T
LOW
Where In Heat Mode: T=SPT-RT
In Cool Mode:
T= RT –SPT
Note:
1. In Heat Mode, the rules in section 4.0.3 have the higher priority.
2. The table above can be represent by a hysteresis curve which will minimize the
switching of the IFAN relay and will minimize the change in IFAN speed:
T [
o
c]
L
M
H
IFAN speed
3
2
1
Summary of Contents for ONG3-17 R410A
Page 1: ...CN Fixed RPM Series REFRIGERANT R410A HEATPUMP REV 01 Oct 2008...
Page 21: ...Pressure Curves Service Manual CN Fixed RPM series 6 2 6 1 2 Heating...
Page 23: ...Pressure Curves Service Manual CN Fixed RPM series 6 4 6 2 2 Heating...
Page 25: ...Pressure Curves Service Manual CN Fixed RPM series 6 6 6 3 2 Heating...
Page 27: ...Sound Level Characteristices Service Manual CN Fixed RPM series 7 2...
Page 29: ...Sound Level Characteristices Service Manual CN Fixed RPM series 7 4...
Page 86: ...EXPLODED VIEWS AND SPARE PARTS LISTS Service Manual CN Fixed RPM series 14 2 17...
Page 119: ...PROTECTION 468100326...
Page 121: ......
Page 122: ...3...
Page 124: ......
Page 125: ......
Page 127: ......