CONTROL SYSTEM
Service Manual-CN Fixed RPM series
A. DEICER ACTIVATION ALGORITHM
Notes:
1. Count LDT while Deicing
2. In first COMP activation (after SB or OFF),
2.1. For WSHP: if OCT < 5
o
c, DI = 10 min, else DI = 20 min
2.2. For all other: if OCT < 0
o
c, DI = 10 min, else DI = 40 min.
COMP to ON
For WSHP
DI = 20 (or 10)
DT = 1
All others:
DI = 40 (or 10)
DT = 5
Activate DDt setting
Routine
Start counting TLD
DTF = 0
OCT < DOC ?
DTF=1
&
OCT < DDT
(during last 3 minutes)
&
ICT < 40 deg
Deicer activation
(see Notes)
TLD > DI
&
OCT < DST
(during last 3 minutes)
Deicer activation;
TLD=DI;
(see Notes)
LDT > DT + TimeD
LDT < DT-TimeD
or
LDT < DTmin
DI = TLD - DIT
DI = TLD + DIT
If (TLD>DI) then
TLD=DI;
DI = TLD;
Yes
Yes
DI < DImin
DI > DImax
DI = DImax
DI = DImin
DT = LDT
1
1
No
No
No
Yes
Yes
Yes
No
No
Yes
Yes
No
No
DDT and DTF information from Deicing
Dynamic Threshold setting routine
Summary of Contents for ONG3-17 R410A
Page 1: ...CN Fixed RPM Series REFRIGERANT R410A HEATPUMP REV 01 Oct 2008...
Page 21: ...Pressure Curves Service Manual CN Fixed RPM series 6 2 6 1 2 Heating...
Page 23: ...Pressure Curves Service Manual CN Fixed RPM series 6 4 6 2 2 Heating...
Page 25: ...Pressure Curves Service Manual CN Fixed RPM series 6 6 6 3 2 Heating...
Page 27: ...Sound Level Characteristices Service Manual CN Fixed RPM series 7 2...
Page 29: ...Sound Level Characteristices Service Manual CN Fixed RPM series 7 4...
Page 86: ...EXPLODED VIEWS AND SPARE PARTS LISTS Service Manual CN Fixed RPM series 14 2 17...
Page 119: ...PROTECTION 468100326...
Page 121: ......
Page 122: ...3...
Page 124: ......
Page 125: ......
Page 127: ......