148
Failure code
Outdoor
digital
display tube:
45
Indoor wired
controller:
2D
Indoor unit LED status
LED5
Failure description:
Communications between outdoor units
failure.
20 times
Outdoor unit LED status
LED1
LED2
Normal
Normal
1. Model
Diagnosis and troubleshooting
Flow Logic III series
Diagnosis
Troubleshooting
2. Abnormity detection method
◆
Incorrect order of outdoor
communication wire;
◆
Incorrect wiring of outdoor
communication wire;
◆
Incorrect terminal
connection of outdoor
communication wire;
◆
Incorrect setting of address
dip switch of outdoor unit;
3. Abnormity confirmation
conditions
No communication for 30s (E)
4. Possible causes
◆
Poor communication
wire: short circuit or
disconnection;
◆
Non-corresponding
communication wire A, B and
C;
◆
Incorrect connection of
outdoor unit communication
port of PCB;
◆
Interference source,
which causes unstable
communication of outdoor
unit.
Replace it correctly by after-
sales personnel on site.
Check if the communication wire
between the outdoor units is normal.
Check if the address DIP switch
of outdoor unit is correct.
Check if there is interference source in the
position where the outdoor unit is installed.
Power off the outdoor unit and research it.
Replace the outdoor unit PCB
Reset it correctly by after-
sales personnel on site.
Clear the interference
source.
N
N
N
Y
Y
Y
N
Summary of Contents for AWAU-YDV1010-H13
Page 1: ...SYJS 03 2017 REV A Edition 2017 03 Service Manual Flow Logic III...
Page 56: ...54 7 Operation range...
Page 102: ...100 Power module driver board 0151800090B and 0151800090...
Page 103: ...101 Filter board MHW505A012...
Page 187: ...Airwell reserves the right to make change without any notice...