160
Failure code
Outdoor
digital
display tube:
111-0, 1, 1
Indoor wired
controller:
6F
Indoor unit LED status
LED5
Failure description:
Overcurrent of module 1 and 2
20 times
Outdoor unit LED status
LED1
LED2
Normal
Normal
1. Model
Failure diagnosis and troubleshooting
Flow Logic III series
Diagnosis
Troubleshooting
2. Abnormity detection method
◆
Check if the module is in
normal conditions and if P and
N is short-circuited to U, V and
W; Measure with diode to see if
there is a voltage drop between
P/N and U/V/W.
◆
Check if the module is
securely fixed and the heat
dissipation is good;
◆
Check if the compressor
winding is normal.
◆
Check if the compressor
wiring UVW is connected
correctly and the inverter board
and module board is securely
wired.
3. Abnormity confirmation
conditions
Overcurrent of module hardware
4. Possible causes
◆
The module alarms failure
as it broke down;
◆
Liquid shock is found in
compressor which results in
overcurrent upon starting or
operating;
◆
The compressor winding is
burned out;
◆
UVW wiring is wrongly
connected or the inverter board
and module board are wired
insecurely.
Check if the supply voltage is normal
Check if the electrical cabinet and
compressor wires are secured, the
UVW is correctly connected and
the variable frequency board and
module board are wired correctly.
Check if the PWM signals
from 6 channels on variable
frequency control board and
IPM driver board are normal.
Check if the power module is normal
Check if the compressor, resistance
and insulation are normal
The compressor is overloading
and check for the causes.
Replace on site by after-sales
personnel.
Replace on site by after-sales
personnel.
Replace the variable frequency
control board.
Replace the power module.
Replace the compressor.
Y
Y
Y
Y
Y
N
N
N
N
N
Summary of Contents for AWAU-YDV1010-H13
Page 1: ...SYJS 03 2017 REV A Edition 2017 03 Service Manual Flow Logic III...
Page 56: ...54 7 Operation range...
Page 102: ...100 Power module driver board 0151800090B and 0151800090...
Page 103: ...101 Filter board MHW505A012...
Page 187: ...Airwell reserves the right to make change without any notice...