Failure code
Outdoor
digital
display tube:
34-0, 1
Indoor wired
controller:
22
Indoor unit LED status
LED5
Failure description:
Outdoor compressor discharging
temperature (Td1, Td2).too high failure
20 times
Outdoor unit LED status
LED1
LED2
Normal
Normal
1. Model
Diagnosis and troubleshooting
Flow Logic III series
Diagnosis
Troubleshooting
2. Abnormity detection method
◆
Check if the temperature
detected via a discharging
temperature sensor is correct.
◆
Check the unit for leakage
or insufficient refrigerant;
◆
Check if the outdoor unit
SV31, SV32, LEVb, etc. can be
normally turned on;
◆
Check the outdoor heat
exchanger of unit for filth
blockage and air inlet & outlet
short circuit when cooling.
◆
Check the indoor heat
exchanger of the unit for filth
blockage and air inlet & outlet
short circuit when heating.
3. Abnormity confirmation
conditions
Toil1/Toil2≥120°C.
4. Possible causes
◆
The oil temperature sensor
is with resistance drift;
◆
The refrigerant in the system
is insufficient;
◆
The outdoor unit LEVb,
SV31 and SV32 cannot be
turned on normally.
◆
The unit condensation
side is with poor heat transfer
function;
◆
The operation environment
is beyond the allowed range.
Replace the discharging
temperature sensor by after-
sales personnel on site.
Check if the resistance of
discharging temperature
sensor is correct.
Check if the refrigerant in the
system is with leakage or insufficient.
Check if the outdoor heat
exchange is normal when
cooling, and check if the
indoor heat exchange is
normal when heating.
Check if the outdoor unit
LEVb, SV31 and SV32 cannot
be turned on normally.
Check if the allowed operation
range is exceeded.
Use the unit in accordance with
its allowed operation range.
Replace it correctly by after-
sales personnel on site and
ensure the refrigerant is enough.
Replace it correctly by after-
sales personnel on site.
Troubleshoot and replace
it correctly by after-sales
personnel on site.
Y
N
Y
N
N
N
Y
Y
Y
Summary of Contents for AWAU-YDV1010-H13
Page 1: ...SYJS 03 2017 REV A Edition 2017 03 Service Manual Flow Logic III...
Page 56: ...54 7 Operation range...
Page 102: ...100 Power module driver board 0151800090B and 0151800090...
Page 103: ...101 Filter board MHW505A012...
Page 187: ...Airwell reserves the right to make change without any notice...