115
②
Heating high pressure control
Target pressure Pd when heating
Remarks
Long piping setting
30kg
Medium piping setting
28kg
Factory default setting
Short piping setting
26kg
During heating, the operating frequency of compressor is fuzzy controlled based on target Pd.
The frequency of compressor goes down and Pd goes down; the frequency of compressor goes up and Pd goes
up.
[Note] For heating capacity, if the high pressure is higher, the capacity is higher. However, if the high pressure is
higher, the COP of unit will be lower.
15.3 Fan control
①
Control of MX7 series DC motor
The air supply speed of outdoor unit can be set from speed 0 to 15 in accordance with the operating mode.
The operating is commonly at speed 1 - 16, and it is CVT (Continuously Variable Transmission) control between
speed 1 and 15.
②
Air supply motor: range of number and rotating speed (unit: rpm)
Rotating Speed No.
12 - 14HP
16HP
18 - 24HP
1
OFF
2
OFF
3
OFF
4
160rpm
*
2
5
190
*
2
6
230
*
2
7
280
*
2
8
330
*
2
9
400 / 400
10
400 / 500
11
520 / 660
12
680 / 680
13
800 / 880
14
880 / 960
Common used Max. value: 15
960
1080
1140
High static pressure: 16
1080
1140
1180
Summary of Contents for AWAU-YDV1010-H13
Page 1: ...SYJS 03 2017 REV A Edition 2017 03 Service Manual Flow Logic III...
Page 56: ...54 7 Operation range...
Page 102: ...100 Power module driver board 0151800090B and 0151800090...
Page 103: ...101 Filter board MHW505A012...
Page 187: ...Airwell reserves the right to make change without any notice...