32
Model
AWAU-YDV1680-H13
AWAU-YDV1680-H13
Outdoor coil
Number of rows
2+2+2
2+2+3
Tube pitch (a)×row pitch (b)
mm
25.4×19.05
25.4×19.05
Fin spacing
mm
1.3
1.3
Fin type (code)
Hydrophilic aluminum
Fin coating type
Optional
Clear lacquer
Clear lacquer
Salt spray test duration
Hour
168
168
Tube outside dia. and type
INNERGROOVE TUBE
mm
Ф8
Ф8
Coil length×height
mm
(1648.2×.1168.4)*2*3
(1648.2×1168.4)*2*2+
(1648.2×1168.4+1648.2×812.)*2
Number of circuits
15*2*3
15*2*2+15*2
Cabinet coating
Coating type
Powder Coating
Powder Coating
Salt spray test duration
Hour
72
72
Sheet metal material
Hot zinc plate
Hot zinc plate
Sheet metal thickness
mm
0.8
0.8
Control panel enclosure IP class
Standard
IP24
IP24
Outdoor air flow (cooling/heating)
m
3
/h
48600 / 45000
48600 / 45000
External static pressure
Pa
82
82
Outdoor sound level (sound pressure level ) (H)
dB (A)
67
67
Outdoor sound level (sound power level ) (H)
dB (A)
85
85
Outdoor unit
Dimension (W*H*D)
mm
(1350×720×2048)*3
(1350×720×2048)*3
Packing (W*H*D)
mm
(1450×826×2225)*3
(1450×826×2225)*3
Net weight
kg
1005
1029
Gross weight
kg
1080
1104
Refrigerant
Type
R410A
R410A
Charged volume*3
kg
30
30
Throttle type
EXV
EXV
Design pressure
MPa
4.15
4.15
Refrigerant piping
Liquid pipe
mm
φ19.05
φ19.05
Gas pipe
mm
φ41.3
φ41.3
Oil pipe
mm
φ9.52
φ9.52
Total pipe length
m
1000
1000
Max. pipe length (Equivalent / actual)
m
190/165
190/165
Max. Diff. indoor/outdoor unit*1
90 (Outdoor higher than indoor)
110 (Indoor higher than outdoor)
Standard
Diff. indoor/outdoor unit
m
50 (Outdoor higher than indoor)
40
(Indoor higher than outdoor)
Max. / standard Diff. indoor/indoor
unit*1
m
30 / 18
30 / 18
Connectable indoor unit ratio*1
%
50%~160%
50%~160%
Maximum indoor units
Piece
64
64
Connection wiring
Max. fuse current
A
210
220
Min. wiring current
A
132.6
138.8
Power wiring
mm
2
/
/
Signal wiring
mm
2
2
Operation range
°C
Cooling: -5~50 Heating: -23~21
Norminal condition: indoor temperature (cooling): 27DB (°C)/19WB (°C), indoor temperature (heating):
20DB (°C)/14.5WB (°C). Outdoor temperature (cooling): 35DB (°C)/24WB (°C), outdoor temperature (heating): 7DB (°C)/6WB (°C) The data is
measured with 7.5m equivalent pipe and 0m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated
sound intensity meter. It is a sound pressure noise level.
*1 If the height difference between the outdoor and indoor units is from 50 to 110m or the height difference between the indoor units is from
18 to 30m or the connectable indoor unit ratio is from 130% to 160%, you Must contact your local distributor/dealer for individual design and
production.
Summary of Contents for AWAU-YDV1010-H13
Page 1: ...SYJS 03 2017 REV A Edition 2017 03 Service Manual Flow Logic III...
Page 56: ...54 7 Operation range...
Page 102: ...100 Power module driver board 0151800090B and 0151800090...
Page 103: ...101 Filter board MHW505A012...
Page 187: ...Airwell reserves the right to make change without any notice...