• Ground wires should be connected correctly (grounded).
• Power supply wire should be connected to power supply terminal board.
• When connected to the power supply terminal board, rounded compression terminal should be adopted.
• Particular wire should be used for connection in wiring. And external force should not be applied on the joint
during fixing.
• Please use proper screwdriver to tighten screws on the binding post. Refer to the below table for tightening
torque of relevant terminal.
If the screws on binding post are tightened excessively, the screws may be broken.
• After completion of the power supply works, please make sure all the connectors and terminals of electrical
components in the instrument box do not fall off.
Tightening torque (N m)
M4 Terminal for signal wire
0.9~1.2
M5
Terminal and ground
wire for power supply
2.00~2.35
Rounded compression joint
Wire
(3) Specifications of outdoor unit power supply:
three-phase power supply of 380V and 50/60Hz
Item
Model
Power
supply
Minimum
cross
section
area of
power
wire
(mm
2
)
Wiring
length
(m)
Circuit
breaker
(A)
Rated current of leakage
circuit breaker (A)
Leakage current (mA)
Operation time (s)
Ground wire
Load
area
(mm
2
)
Screw
type
Independent power supply
AWAU-YDV250-H13
3PH,
380V,
50/60Hz
10
92
40
40A, 100mA, below 0.1s
5.5
M6
AWAU-YDV280-H13
10
92
40
40A, 100mA, below 0.1s
5.5
M6
AWAU-YDV335-H13
(DROP ONLY)
10
92
40
40A, 100mA, below 0.1s
5.5
M6
AWAU-YDV400-H13
16
92
50
50A, 100mA, below 0.1s
5.5
M6
AWAU-YDV450-H13
16
92
60
60A, 100mA, below 0.1s
5.5
M6
AWAU-YDV504-H13
16
92
70
70A, 100mA, below 0.1s
5.5
M6
AWAU-YDV560-H13
16
92
70
70A, 100mA, below 0.1s
5.5
M6
AWAU-YDV615-H13
(DROP ONLY)
25
92
80
80A, 100mA, below 0.1s
5.5
M6
AWAU-YDV680-H13
25
92
80
80A, 100mA, below 0.1s
5.5
M6
• Power wire of outdoor unit should be well fixed and connected by rounded compression joint. It is strictly
prohibited to be connected to line bank.
• All the outdoor units should be grounded.
• Power wire should be thickened if its length is out of range.
Summary of Contents for AWAU-YDV1010-H13
Page 1: ...SYJS 03 2017 REV A Edition 2017 03 Service Manual Flow Logic III...
Page 56: ...54 7 Operation range...
Page 102: ...100 Power module driver board 0151800090B and 0151800090...
Page 103: ...101 Filter board MHW505A012...
Page 187: ...Airwell reserves the right to make change without any notice...