132
Failure code
Outdoor
digital
display tube:
27-0, 1
Indoor wired
controller:
1B
Indoor unit LED status
LED5
Failure description:
Outdoor compressor oil temperature too
high failure(Toil1 and Toil2)
20 times
Outdoor unit LED status
LED1
LED2
Normal
Normal
1. Model
Failure diagnosis and troubleshooting
Flow Logic III series
Diagnosis
Troubleshooting
2. Abnormity detection method
◆
Check if the temperature
detected by the oil temperature
sensor is correct;
◆
Check the unit for leakage
or insufficient refrigerant;
◆
Check if the outdoor unit
SV31, SV32, LEVb, etc. can be
normally turned on;
◆
Check the outdoor heat
exchanger of this unit for filth
blockage and inlet & outlet air
blockage.
◆
Check the indoor heat
exchanger of this unit for filth
blockage and inlet & outlet air
blockage when cooling.
3. Abnormity confirmation
conditions
Toil1/Toil2≥120°C.
4. Possible causes
◆
The oil temperature sensor
is with resistance drift;
◆
The refrigerant in the system
is insufficient;
◆
The outdoor unit LEVb,
SV31, SV32, etc. cannot be
turned on normally;
◆
The unit condensation
side is with poor heat transfer
function.
◆
The operation environment
is beyond the allowed range.
Replace the oil temperature
sensor by after-sales personnel
on site.
Check if the resistance of oil
temperature sensor is correct
Check if the refrigerant in the
system is with leakage or insufficient
Check if the outdoor heat
exchange isnormal when cooling,
and check if the indoor
heating is normal when heating
Check if the outdoor unit LEVb, SV31
and SV32 can be turned on normally
Check if it is beyond the
allowed operation range of unit.
Use the unit in accordance
with its allowed range.
Replace it correctly by after-
sales personnel on site and
ensure refrigerant is enough.
Replace it correctly by after-
sales personnel on site.
Troubleshoot and replace
it correctly by after-sales
personnel on site.
N
Y
N
Y
Y
Y
Y
N
N
Summary of Contents for AWAU-YDV1010-H13
Page 1: ...SYJS 03 2017 REV A Edition 2017 03 Service Manual Flow Logic III...
Page 56: ...54 7 Operation range...
Page 102: ...100 Power module driver board 0151800090B and 0151800090...
Page 103: ...101 Filter board MHW505A012...
Page 187: ...Airwell reserves the right to make change without any notice...