4
Appearance
Power
supply
(Ph, V, Hz)
AWAU-YDV1360-H13
Capacity(kW)
Refrigerant
3Ph,380V
50/60Hz
AWAU-YDV1408-H13
140.8
R410A
AWAU-YDV1460-H13
146
AWAU-YDV1514-H13
151.4
AWAU-YDV1570-H13
157
AWAU-YDV1624-H13
162.4
AWAU-YDV1680-H13
168
AWAU-YDV1735-H13 (DROP
ONLY) (DROP ONLY)
173.5
AWAU-YDV1800-H13
180
AWAU-YDV1855-H13 (DROP
ONLY)
185.5
AWAU-YDV1920-H13
192
AWAU-YDV1975-H13 (DROP
ONLY) (DROP ONLY) (DROP
ONLY)
197.5
AWAU-YDV2040-H13
204
Note:
The single module capacity range of Flow Logic III is from 8HP to 24 HP. In one system
too much difference of capacity will cause of bad oil return.
To protect the unit, adding the following limit in the PCB program of the outdoor unit:
In one system the difference of capacity between any two outdoor units can’t be more
than 4HP.
If in one system the difference of capacity is more than 4HP, the outdoor PCB will
display “80” failure code and can’t run.