40-7705ii-UM
Page 2
Rev. 1 June 11, 2018
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND
OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply
with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems,
UL 864, certain programming features or options must be limited to specific values or not used
at all as indicated below.
Program
Permitted in
Possible
Feature or Option
UL 864 (Y/N)
settings
Settings permitted in UL 864
Alarm Automation
Y
0-90
As configured by UL 1981
Heartbeat Signal
Central-Station Automation
Frequency:
Systems Requirements
Serial or IP
Data Type:
Y
Security, GPS, USDI,
Security
Others in pull down menu
Old Alarm Delivery
Y
All, Subscriber controlled
Options
Never
All
Radio Packet Life
Y
0-99
0 – No Time Out for Alarm, Trouble or
Restoral
Software Version:
Instructions to view the software version are in Section 3.1.1 LCD Display and Software Version.
Notes:
1.
For Alarm Automation references throughout this manual:
Alarm Automation output must be connected to a UL 1981 Listed Alarm Automation System
2.
For UL Central Station Burglar Alarm applications:
Opening/Closing Signals shall be sent using an alternate communication means that provides for
premises acknowledgement (ring back)
3.
This product shall be installed in accordance with NFPA 72, NEC,
UL 827 and all applicable local codes
4.
For compliance with UL Central Station Burglar Alarm applications:
A computer workstation is required to be able to determine subscriber status. The workstation
shall be UL Listed ITE equipment.