Notes:
Power Line, router/ switch, and telephone connections shall not leave the room
where the AES equipment is installed. This must be accomplished by co-
locating outlets and interfacing equipment in the room where AES equipment
resides.
7705ii must be installed in a UL Listed metal rack-mounting cabinet that
complies with UL-60950 standard for IT equipment. The rack mount cabinet
must be provided with integral outlets and the ability to connect AC input via
conduit. All wiring exiting the cabinet must be in electrical conduit. Be sure
non-power limited and power limited wiring are separated by at least 1/4 inch.
All equipment shall be connected to a UL Listed UPS (UL 864) or UL 1481
power supply. In addition, the central station shall have a generator to
maintain power for the receiving equipment and environmental controls for a
period up to 24 hours or longer.
A UL Listed UPS or generator to supply 24 hours of standby must be installed
and utilized at the monitoring station. If the primary power source at the
monitoring station is lost or otherwise faulted, this condition must be obvious
to the operator on duty.
Equipment Location: A UL 7705ii MultiNet Receiver must be installed in a
room where operators can properly hear the Audio Alert Sounder.
When connecting the 7705ii MultiNet Receiver’s modem to a telephone line, a
UL 497A Secondary Protector is required to be installed on the incoming lines.
Installation shall be in accordance with the NEC Article 800, the
manufacturers installation instructions and in accordance with all local codes.
When connecting the 7705ii MultiNet Receiver’s Ethernet ports to a network,
a UL 497B Secondary Protector is required to be installed on the Ethernet
cable. Installation shall be in accordance with the NEC Article 800, the
manufactures installation instructions and in accordance with all local codes.
4.1
Software Installation:
All necessary software is pre-installed on your 7705ii.
If your system has a catastrophic failure it may require the reinstallation of the Linux
operating system and the specialized IP-Link software programs. BIOS settings should
also be checked to confirm that the unit would initialize and operate properly. Routine
backing up of the databases to another storage device would be essential in any
successful reinstallation or recovery process.
Contact AES Technical Support if you need assistance with software installation or
BIOS settings.