40-7705ii-UM
Page 111
Rev 1 June 11, 2018
Appendix F
Printer Messages Produced by the MultiNet receiver
For many events that occur in the MultiNet system, messages are created and printed on
the attached printer. These events are be created by the communicators (Subscribers) in
the MultiNet system, IP-Link Transceivers and by the MultiNet Receiver itself. There
are also a number of reports that can be printed. Following is a list and description of
some of those messages.
Controls for what is printed are located within the Business Unit configurations and
throughout the MultiNet menu system.
Print format for Events such as alarm and fault messages:
When an event is reported to the MultiNet receiver and the receiver determines that it
needs to be printed the following general format is used.
Day Mmm dd hh:mm:ss YYYY - - Message…
The printed line begins with date and time stamp indicating when the MultiNet Receiver
received the message.
Day
3 letter abbreviation for day of week
Mmm
3 letter abbreviation for month of year
dd
Date of month
hh:mm
Hour of day and minute of the hour
ss
Second of the minute
YYYY
Four digit Year
Following the Date stamp is a three-letter code identifying the device or origin of the
reported message. Following is a list of those codes:
IPL
IP-Link message
LPT
Printer fault
MDM
Modem
RFI
Radio Frequency Interference message
OFF
Offline message
- -
System Message
Message…= This portion varies depending on the type of event or message that is being
printed. Examples Follow:
-- IPLink 0000####, Power On Reset
-- E140 ACCT 9371 ZONE C006
11 9371 18 A140 00 C006
(Tracking=21924)
-- IPLink 00002222, Starting Modem Test!
Manual Acknowledge (Tracking=21924) -> 11 9371 18 A140 00 C006
-- Alarm Automation System is up! (serial)
-- IPL 1111 Battery Voltage - Fault
Alarm codes printed are defined in Appendix E