Event plus Zone, Status and Fault Codes, Produced for Events Created by Subscribers:
A 000
Automatic Supervisory Check-In
10R1 ACCT A 000
A NNN Alarm Signal Zone NNN ٭
10R1 ACCT A nnn
SA NNN Prior Alarm zone NNN ٭ Input still active. Reported during Status Request or Check-In
10R1 ACCTSA nnn
R NNN Alarm or Zone trouble Restoral or input to normal - Zone NNN ٭
10R1 ACCT R nnn
Y 800
Diagnostic Fault - “No Faults, Unit OK or Restoral of all Prior Faults”
10R1 ACCT Y 800
see Diagnostic Faults below
Y 801
Diagnostic Fault - “Low Battery” - Voltage less than 11.0V
10R1 ACCT Y 801
Y 802
Diagnostic Fault - “RAM Data error or RAM corrupted” -
10R1 ACCT Y 802
Zone activation will not be reported (Sub. V1.71+). Reprogram Unit
Y 803
Diagnostic Fault - “7050 - U11 RAM Chip Internal Battery Bad”
10R1 ACCT Y 803
“7050E - EEPROM corrupted, or not present”
Y 804
Diagnostic Fault - “7050E - A to D Converter Faulted” -
10R1 ACCT Y 804
Zone activation will not be reported (Sub. V1.71+).
Y 805
Diagnostic Fault - “Modem Chip Failed or missing” - 7050 U9
10R1 ACCT Y 805
Y 806
Diagnostic Fault - “Timing Error between CPU and Modem”
10R1 ACCT Y 806
Y 807
Diagnostic Fault - “Ram Chip Read/Write test Failure” - 7050 U11
10R1 ACCT Y 807
Y 808
Diagnostic Fault - “Modem Loop back Failed” -7050 U9”
10R1 ACCT Y 808
Y 809
Diagnostic Fault - “7050E - AC Fail” or “DC voltage supplied by AC has dropped below 12V”
10R1 ACCT Y 809
SY 80n
Prior Diagnostic Fault still active. Reported during Check-In.
10R1 ACCT Y 80n
(n = 1-9, see Diagnostic Faults above)
T 901
Trouble - “Watchdog or Push-button Reset”
10R1 ACCT T 901
T 902
Trouble - “Power-On Reset”
10R1 ACCT T 902
R 903
Trouble - “Communication time-out or Acknowledge Delay”
10R1 ACCT T 903
T 904
Trouble -
10R1 ACCT T 904
T 905
Trouble - “IntelliTap phone line cut.”
10R1 ACCT T 905
R 905
Trouble Restore- “IntelliTap phone line restore.”
10R1 ACCT T 905
T 906
Exception - “Unit or Subscriber Failed to Check-In”
10R1 ACCT T 906
Generated by MultiNet Receiver on failure to receive test message within specified time frame.
R 906
Exception Restoral - “Unit or Subscriber on Line” or “… has now checked-in”
10R1 ACCT R 906
T NNN
Zone Trouble Signal. Zone NNN ٭
10R1 ACCT T nnn
ST NNN Prior Zone Trouble zone NNN ٭ Input still active. Reported during Status Request or Check-In
10R1 ACCTST nnn