40-7705ii-UM
Page 102
Rev 1 June 11, 2018
Event Code Usage for Ademco 685 Output Emulation
Event
Code
Universal Description
AES specific Usage
110
Fire
Subscriber Zone designated for Fire
130
Burglary
Subscriber Zone designated for Burglary
140
Alarm
Subscriber’s Zone Input Off-Normal
145
Expansion module tamper
7170 IP-Link Transceiver Enclosure Tamper
(Zone/contact = 906)
200
Fire Supervisory
Subscriber Zone designated for Fire Supervisory
300
System Trouble
Subscriber Zone designated for Fire Trouble
300
System Trouble
MultiNet Receiver’s LCD or LCD offline
(for LCD Zone/contact = 902) (for LED Zone/contact = 903)
301
AC Loss
IP-Link AC input failure (Zone/contact = 912)
302
Low system battery
IP-Link low battery condition (Zone/contact = 911)
305
System reset
Watchdog, Pushbutton or Power–On Reset
(Watchdog or pushbutton Zone/contact = 901) (Power-on Zone/contact = 902)
307
Self Test Failure
Diagnostic Fault (Zone/contact = Fault Code)
(Zone 800 = restoral of all Prior faults) (See below for codes 801-809)
309
Battery test failure
Charger Voltage low (Zone/contact = 910)
336
Local printer failure
Printer off-line (Zone/contact = 904)
350
Communications trouble
RF Interference (Zone/contact = 906)
351
Telco 1 Fault / IntelliTap detected phone line cut (Zone/contact = 905)
353
Long range radio xmitter fault
Multiple IP-Links with same Unit ID
(Zone/contact = 906)
354
Failure to communicate event
Exception – Unit failed to Check-In
(Zone/contact = 906)
Generated by Receiver on failure to receive test message within specified time frame
354
Failure to communicate event
Exception – TCP/IP Supervision Failure
(Zone/contact = 906)
354
Failure to communicate event
Exception – MultiNet Modem Failure
(Zone/contact = 907)
354
Failure to communicate event
Exception – IP-Link Modem Failure
(Zone/contact = 908)
354
Failure to communicate event
Exception – Unit NetCon is 6 or 7
(Zone/contact = 915)
355
Loss of Radio Supervision
IP-Link RF Ping Failure (Zone/contact = 906)
356
Loss of central polling
Acknowledge Delay or Communication timeout
(Zone/contact = 903)
357
Antenna Supervision Module
IP-Link antenna cut/restoral (Zone/contact = 916)
370
Protection Loop
Zone Trouble. (Zone/contact ID = 001 to 008)
370
Protection Loop
7744 Battery Charger Trouble (Zone/contact ID = 009)
370
Protection Loop
7744 Ground Fault (Zone/contact ID = 010)
602
Periodic test report
Automatic Supervisory Check-In