Chapter
4
Chapter 4 Command Set 4-43
4.6.5
$AAX0TTTTDD
Name
Write Safety Value
Description
Force the DO channels to safety status when communication
is in time-out and over pre-defined period.
Syntax
$AAX0TTTTDD(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address which is to be accessed.
X0 is to write the safety value command.
TTTT is the time, and it is 100ms per number. Turn off the
Communication WDT when TTTT is set to 0.
DD is the two-hexadecimal character representing the desired
input safety value. For Example: 7A
The meaning of 7A is as follows:
Adam-4117 channel no. 7 6 5 4 3 2 1 0
Digital value
0 1 1 1 1 0 1 0
7A means that the status of channels 1, 3, 4, 5, 6 are ON, and
the rest are OFF.
(cr) is the terminating character, carriage return (0Dh).
Response
>(cr) if the command was valid.
?AA(cr) if an invalid command has been issued.
There is no response if the module detects a
syntax or communication error, or even if the
specified address does not exist.
> is a delimiter character indicating that a valid
command was received.
? is a delimiter character indicating that the
command was invalid.
AA (range 00-FF) represents the responding 2-
character hexadecimal address of the digital I/O module.
Summary of Contents for ADAM 4100
Page 1: ...ADAM 4100 Industrial Grade Data Acquisition Modules User s Manual ...
Page 5: ...Introduction 1 ...
Page 9: ...Installation Guideline 2 ...
Page 24: ...I O Modules 3 ...
Page 25: ......
Page 37: ...Chapter 3 I O Modules 3 13 I O Modules Figure 3 10 Digital Output used with SSR ADAM 4150 ...
Page 40: ...Command Set 4 ...
Page 41: ......
Page 51: ......
Page 105: ...Calibration 5 ...
Page 109: ...5 4 ADAM 4100 Series User s Manual ...
Page 110: ...Utility Software A ...
Page 111: ......
Page 121: ...ADAM 4100 I O Modbus Mapping Table B ...
Page 131: ...Technical Diagrams C ...
Page 134: ...C 4 ADAM 4100 Series User s Manual Appendix C Figure C 3 DIN Rail Mounting ...
Page 136: ...C 6 ADAM 4100 Series User s Manual Appendix C Figure C 5 Panel Mounting ...
Page 138: ...Data Formats and I O Ranges D ...
Page 142: ...RS 485 Network E ...
Page 143: ......
Page 150: ...How to use the Checksum feature F ...
Page 154: ...Changing Configuration to Modbus Protocol G ...