Appendix D
D.1.2 Percent of FSR
This mode is used by setting bits 0 and 1 of the data format/checksum
/integration time parameter to 01. The format used in Percent of FSR
consists of a plus (+) or minus (-) sign followed by five decimal digits
including a decimal point. The maximum possible resolution is 0.01%
with the decimal point fixed.
Data are given as the ratio of the input signal to the full-scale range.
Example 1
The input value is +2.0 V. The input module is configured for a range
of ±5 V. The response to the Analog Data In command is as follows:
+040.00 (cr)
The full calibrated voltage range ranges from -100% to 100% as
voltage input ranges are always bipolar. A ±5 V input would range
from -5 V (-100%) to 5 V (100%).
In this example the input is represented by +40% of the full-scale range
which equals to (+(40/100) x 5 V = +2.0 V) the actual input value.
Example 2
The input value is 652.5
o
C, and a type E thermocouple (0
o
C to 1000
o
C)
is configured in the analog input module. The response to the Analog
Data In command is: +065.25 (cr)
The result shows that the value of the input (652.5
o
C) is 65.25% of the
full-scale range (1000
o
C).
Thermocouple input ranges are always assumed to be bipolar with zero
being the point of symmetry. This holds true regardless of the specified
range of operation. For example, when we use a type J thermocouple
(0
o
C to 760
o
C), 760
o
C corresponds to +100% and 0
o
C corresponds to
0%. Even if 0
o
C lies outside of the specified operation range for the
thermocouple, zero will remain as the point of symmetry. For instance,
a type B thermocouple is specified for operation from +500
o
C to +1800
o
C. In this case +1800
o
C corresponds to + 100% and 500
o
C corresponds
to +27.77%.
The percentage is related to the full span of the configured range. For
instance, a nickel RTD is specified for -80
o
C to +100
o
C. Then, the
lower value of -80
o
C equals to 0% of span and the upper value of
+100
o
C equals to 100% of span.
Appendix D Data Formats and I/O Ranges D-
3
Summary of Contents for ADAM 4100
Page 1: ...ADAM 4100 Industrial Grade Data Acquisition Modules User s Manual ...
Page 5: ...Introduction 1 ...
Page 9: ...Installation Guideline 2 ...
Page 24: ...I O Modules 3 ...
Page 25: ......
Page 37: ...Chapter 3 I O Modules 3 13 I O Modules Figure 3 10 Digital Output used with SSR ADAM 4150 ...
Page 40: ...Command Set 4 ...
Page 41: ......
Page 51: ......
Page 105: ...Calibration 5 ...
Page 109: ...5 4 ADAM 4100 Series User s Manual ...
Page 110: ...Utility Software A ...
Page 111: ......
Page 121: ...ADAM 4100 I O Modbus Mapping Table B ...
Page 131: ...Technical Diagrams C ...
Page 134: ...C 4 ADAM 4100 Series User s Manual Appendix C Figure C 3 DIN Rail Mounting ...
Page 136: ...C 6 ADAM 4100 Series User s Manual Appendix C Figure C 5 Panel Mounting ...
Page 138: ...Data Formats and I O Ranges D ...
Page 142: ...RS 485 Network E ...
Page 143: ......
Page 150: ...How to use the Checksum feature F ...
Page 154: ...Changing Configuration to Modbus Protocol G ...