4.6.21
@AACACj
Name
Clear Latch Alarm
Description
Both alarm states (High and Low) of the counter module
are set to OFF.
Syntax
@AACACj(cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter module.
CA is the Clear Latch Alarm command
Cj is the channel j
(cr) represents terminating character, carriage return (0Dh)
Response
!AA(cr) if the command was valid
?AA(cr) if an invalid command has been issued.
There is no response if the module detects a
syntax or communication error, or even if the specified
address does not exist.
! is a delimiter character indicating that a valid command
was valid
AA represents the 2-character hexadecimal address of the
responding counter module.
(cr) represents terminating character, carriage return (0Dh)
Example
command: @05CAC1(cr)
response: !05(cr)
The counter module at address 05h and channel 1 are
instructed to set both alarm states (High and Low) to OFF.
The module confirms the execution.
Summary of Contents for ADAM 4100
Page 1: ...ADAM 4100 Industrial Grade Data Acquisition Modules User s Manual ...
Page 5: ...Introduction 1 ...
Page 9: ...Installation Guideline 2 ...
Page 24: ...I O Modules 3 ...
Page 25: ......
Page 37: ...Chapter 3 I O Modules 3 13 I O Modules Figure 3 10 Digital Output used with SSR ADAM 4150 ...
Page 40: ...Command Set 4 ...
Page 41: ......
Page 51: ......
Page 105: ...Calibration 5 ...
Page 109: ...5 4 ADAM 4100 Series User s Manual ...
Page 110: ...Utility Software A ...
Page 111: ......
Page 121: ...ADAM 4100 I O Modbus Mapping Table B ...
Page 131: ...Technical Diagrams C ...
Page 134: ...C 4 ADAM 4100 Series User s Manual Appendix C Figure C 3 DIN Rail Mounting ...
Page 136: ...C 6 ADAM 4100 Series User s Manual Appendix C Figure C 5 Panel Mounting ...
Page 138: ...Data Formats and I O Ranges D ...
Page 142: ...RS 485 Network E ...
Page 143: ......
Page 150: ...How to use the Checksum feature F ...
Page 154: ...Changing Configuration to Modbus Protocol G ...