Chapter 3 I/O Modules 3-7
I/O Modules
Specification
Analog Input
Effective Resolution: 16-bit
Channel: 8 differential
ASCII command and Modbus protocol
Input type & range:
Thermocouple
J 0
~
760
o
C
K
0 ~ 1370
o
C
T -100
~
400
o
C
E
0
~
1000
o
C
R 500 ~ 1750
o
C
S 500
~
1750
o
C
B 500 ~ 1800
o
C
Voltage mode
±15mV, ±50mV, ±100mV, ±500mV, ±1V, ±2.5V
Current mode
±20 mA, +4~20 mA
Isolation Voltage 3000 V
DC
Fault and Over voltage: Protection up to ±60V
Sampling Rate: 100 samples/sec (Max).
Input Impedance 20 M
Ω
Accuracy of voltage mode : ±0.1% or better
Accuracy of Current mode and high speed mode: ±0.2% or better
Zero Drift: ±6µV/° C
Span Drift: ±25 ppm/° C
CMR @ 50/60 Hz 92 dB
min.
Built-in Dual Watchdog Timer
Built-in TVS/ESD Protection
Power Consumption 0.5W @
24 VDC
Summary of Contents for ADAM 4100
Page 1: ...ADAM 4100 Industrial Grade Data Acquisition Modules User s Manual ...
Page 5: ...Introduction 1 ...
Page 9: ...Installation Guideline 2 ...
Page 24: ...I O Modules 3 ...
Page 25: ......
Page 37: ...Chapter 3 I O Modules 3 13 I O Modules Figure 3 10 Digital Output used with SSR ADAM 4150 ...
Page 40: ...Command Set 4 ...
Page 41: ......
Page 51: ......
Page 105: ...Calibration 5 ...
Page 109: ...5 4 ADAM 4100 Series User s Manual ...
Page 110: ...Utility Software A ...
Page 111: ......
Page 121: ...ADAM 4100 I O Modbus Mapping Table B ...
Page 131: ...Technical Diagrams C ...
Page 134: ...C 4 ADAM 4100 Series User s Manual Appendix C Figure C 3 DIN Rail Mounting ...
Page 136: ...C 6 ADAM 4100 Series User s Manual Appendix C Figure C 5 Panel Mounting ...
Page 138: ...Data Formats and I O Ranges D ...
Page 142: ...RS 485 Network E ...
Page 143: ......
Page 150: ...How to use the Checksum feature F ...
Page 154: ...Changing Configuration to Modbus Protocol G ...