Command Set
4-30 ADAM 4100 Series User’s Manual
4.4.19
$AA3
Name
Returns the value of the CJC sensor
Description
Instructs the analog input module to read its CJC (Cold
Junction Compensation) sensors and to return the acquired
data.
Syntax
$AA3(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address which contains the CJC Status you wish to retrieve.
3 is CJC Status command.
(cr) is the terminating character, carriage return (0Dh).
Response
>data(cr) if the command is valid.
?AA(cr) if an invalid command was issued.
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
! is a delimiter character indicating that a valid command
was received.
? is a delimiter character indicating that the command was
invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of an analog input module.
(data) is the value that is retrieved by the module by reading
its CJC sensor. The data format, in degrees Celsius, consists
of a “+” or “-” sign followed by five decimal digits and a
fixed decimal point. The resolution of the data is 0.1 oC.
(cr) is the terminating character, carriage return (0Dh).
Example
command: $093(cr)
response: >+0036.8(cr)
The command requests the analog input module at address
09h to read its CJC sensor and to return the data.The analog
input module at address 09h responds with 36.8
o
C.
Summary of Contents for ADAM 4100
Page 1: ...ADAM 4100 Industrial Grade Data Acquisition Modules User s Manual ...
Page 5: ...Introduction 1 ...
Page 9: ...Installation Guideline 2 ...
Page 24: ...I O Modules 3 ...
Page 25: ......
Page 37: ...Chapter 3 I O Modules 3 13 I O Modules Figure 3 10 Digital Output used with SSR ADAM 4150 ...
Page 40: ...Command Set 4 ...
Page 41: ......
Page 51: ......
Page 105: ...Calibration 5 ...
Page 109: ...5 4 ADAM 4100 Series User s Manual ...
Page 110: ...Utility Software A ...
Page 111: ......
Page 121: ...ADAM 4100 I O Modbus Mapping Table B ...
Page 131: ...Technical Diagrams C ...
Page 134: ...C 4 ADAM 4100 Series User s Manual Appendix C Figure C 3 DIN Rail Mounting ...
Page 136: ...C 6 ADAM 4100 Series User s Manual Appendix C Figure C 5 Panel Mounting ...
Page 138: ...Data Formats and I O Ranges D ...
Page 142: ...RS 485 Network E ...
Page 143: ......
Page 150: ...How to use the Checksum feature F ...
Page 154: ...Changing Configuration to Modbus Protocol G ...