AVERTISSEMENT:
Ne pas mettre l’appareil AE 3TL en marche s’il n’a pas été mis à la terre.
To Operate the AE 3TL Inverter for the First Time
1. Verify that the AC, DC, and ground connections are correctly and securely
installed.
2. Verify that the connection box cover is secure.
3. Close the AC system circuit breakers or insert the external main fuse.
4. Turn the DC disconnect to the
ON
position.
If the solar modules are receiving sufficient sunlight and no fault exists, the
following sequence will occur:
◦ Self test: All status LEDs light up indicating system initialization during
which the PV array is checked for wire insulation integrity. If the wire
insulation is damaged, the inverter will not start and displays a fault. Before
clearing the fault and restarting the inverter, check all PV wiring for nicks,
pinches, and breaks. On first time startup, this process may take as long as an
hour.
◦ Initialization: Status LED
Ready
flashes. The display is lit with the following
information:
F1
F2
ESC
READY
ON
ALARM
EARTH FLT
PAC
0 W
UAC
0.0 V
UDC
0 V
y day
0.0 kWh
Initializing
F1 - Menu
5. Verify that the initialization procedure is complete by checking the following:
◦
ON
LED is continuously lit.
◦ The display begins providing data.
The inverter electronics, the control panel, display, and operating buttons are
active when DC voltage is applied since they are supplied exclusively from the
DC input.
Advanced Energy
5‑2
Operating
570-1003552-05A
Summary of Contents for AE 3TL 1000 Series
Page 2: ......
Page 12: ...Advanced Energy xii 570 1003552 05A List of Tables...
Page 14: ...Advanced Energy xiv 570 1003552 05A List of Figures...
Page 26: ...Advanced Energy 1 12 Safety and Product Compliance Guidelines 570 1003552 05A...
Page 64: ...Advanced Energy 4 28 Installing 570 1003552 05A...
Page 86: ...Advanced Energy 6 4 Operating the Arc Fault Detection Unit 570 1003552 05A...
Page 92: ...Advanced Energy 7 6 Data Monitoring and Controls 570 1003552 05A...
Page 110: ...Advanced Energy 9 14 Troubleshooting and Solar Energy Technical Support 570 1003552 05A...
Page 116: ...Advanced Energy A 6 Specifications 570 1003552 05A...
Page 120: ...Advanced Energy B 4 System and Mechanical Diagrams 570 1003552 05A...